Configure the Gateway
104S
♦
ProLinx Gateway
Protocol Manual
(Firmware v3.00 and later)
Page 28 of 157
ProSoft Technology, Inc.
January 22, 2010
2.2.3 Default Command Qualifier
S
HORT
P
ULSE
(1)
,
L
ONG
P
ULSE
(2)
, or
P
ERSISTENT
O
UTPUT
(3)
The protocol specification defines values for a Qualifier Flag, which is part of every
command message, and associates those values to specific command (control)
points. The value zero(0) is specified as
U
NDEFINED
. This parameter sets the default
output type to use for incoming Command Point executions where the Qualifier Flag
value is U
NDEFINED
.
2.2.4 Override Command Qualifier
N
O
,
S
HORT
P
ULSE
,
L
ONG
P
ULSE
, or
P
ERSISTENT
O
UTPUT
This parameter allows you to set a specific output type for all incoming command
messages, regardless of the Qualifier Flag value contained in the message. Set this
parameter to
N
O
to use the output type specified by the Qualifier Flag received in the
command message. If this parameter is set to any of the other options, the value
received in the Qualifier Flag is ignored and the selected output type will be used for
all command executions.
2.2.5 Point
Count
Point Count configuration ranges in the following configuration items are based on
the assumption that you will be using only one of the available data types for your
application. The number of point counts you configure will have an effect on gateway
performance, in particular the accuracy of the gateway’s internal clock.
Summary of Contents for ProLinx 104S
Page 4: ......