104S
♦
ProLinx Gateway
Configure the Gateway
(Firmware v3.00 and later)
Protocol Manual
ProSoft Technology, Inc.
Page 31 of 157
January 22, 2010
2.2.7 Parameter
Offset
This parameter specifies the Information Object Address (IOA) Offset to normalized
points parameter data. The value entered is added to the IOA for the associated
point to compute the parameter IOA address.
The Client may send a "Parameter of Measured Normalized" or "Parameter of
Measured Scaled" command using the parameter IOA in order to change the
threshold deadband values for specific points.
For example, if the 104S configuration sets two M_ME_NA points with IOA of 600
and 601 and a M_ME_NA Parameter Offset value of 2000, the threshold deadband
parameters for those points would be written to IOA addresses 2600 and 2601.
Note:
The Low Limit and High Limit threshold values are always calculated based on the threshold
deadband value as described in the following table.
Point Value
Threshold
Determined by the deadband set in the configuration file or altered by the write
command.
Low Limit
Last reported event value - threshold.
High Limit
Last reported event value + threshold.