Configure the Gateway
104S
♦
ProLinx Gateway
Protocol Manual
(Firmware v3.00 and later)
Page 38 of 157
ProSoft Technology, Inc.
January 22, 2010
2.15 [C_BO_NA_1
104]
This section defines the 32-bit bitstring command database for the server emulated.
This information is sourced from the remote client and is transferred to the database.
The control value can be associated with a monitored point as described in the
previous example.
This section takes the following parameters:
Point
#:
DB
Address:
Monitor
Point
#:
Monitor
DB
Addr:
Each point is four, 8-bit bytes and the DB Address value corresponds to the double-
word offset in the gateway memory database. For additional information on how to
set these parameters, see the 104S Tutorial and Reference chapters of this manual.
2.16 [C_SE_NA_1
104]
This section defines the normalized setpoint database for the server emulated. This
information is sourced from the remote client and is transferred to the database. You
can associate a command with a monitored normalized database value to coordinate
the command/monitor operation. You must enter the correct Monitor Point # (IOA)
and Monitor DB Addr values in the table. If the Require Select parameter is not set to
zero, a select command must be received before an execute command will be
processed.
This section takes the following parameters:
Point
#
DB
Address
Monitor
Point
#
Monitor
DB
Addr
Require
Select
Each point is one, 16-bit word and the DB Address value corresponds to the word
offset in the gateway memory database. For additional information on how to set
these parameters, see the 104S Tutorial and Reference chapters of this manual.
Summary of Contents for ProLinx 104S