If the highest bit (bit 31) is set, data will be produced by the driver for the specified
point at the rate set for periodic data generation. Bit 30 (0x40000000) enables
scanning of this point for event generation. If the bit is clear and the data type is set
for scanning, events will be generated for the point. If the bit is set, events will not be
generated for the point. This feature can be used to select which points will generate
events for the controlling station and can get rid of event data that is not important to
the application.
2.20 CommonNet Data Map
The
[D
ATA
M
AP
]
section allows you to copy data between areas in the gateway's
internal database.
You can copy a maximum of 100 registers per
Data Map
command, and you can
configure a maximum of 200 separate copy commands.
For example, you can copy data from the error or status tables in upper memory to
internal database registers in the User Data memory area.
You can also rearrange the byte and/or word order during the copy process, for
example, to convert floating-point values to the correct format for a different protocol.
You can also use the
Data Map
to condense widely dispersed data into one
contiguous data block, making it easier to access.