104S
♦
ProLinx Gateway
IEC-60870-5-104 (104S) Protocol Implementation
(Firmware v3.00 and later)
Protocol Manual
ProSoft Technology, Inc.
Page 55 of 157
January 22, 2010
If the highest bit (bit 31) is set, data will be produced by the driver for the specified
point at the rate set for periodic data generation. Bit 30 (0x40000000) enables
scanning of this point for event generation. If the bit is clear and the data type is set
for scanning, events will be generated for the point. If the bit is set, events will not be
generated for the point. This feature can be used to select which points will generate
events for the controlling station and can get rid of event data that is not important to
the application.
The gateway will periodically send all points configured for periodic/cyclic poll
(0x80000000) at every x milliseconds, where x is configured with the following
parameter: