104S
♦
ProLinx Gateway
IEC-60870-5-104 (104S) Protocol Implementation
(Firmware v3.00 and later)
Protocol Manual
ProSoft Technology, Inc.
Page 65 of 157
January 22, 2010
M_BO_NA
A Monitored 32-bit Bitstring point occupies two words and uses double-word
addressing.
For example, if you configured the following points:
The following table describes how these points would be stored in the gateway
memory database.
Inf. Object Address
Gateway Database Address
600
Words 2000 and 2001 (Double-word address 1000)
601
Words 2002 and 2003 (Double-word address 1001)
602
Words 2004 and 2005 (Double-word address 1002)
Summary of Contents for ProLinx 104S