104S
♦
ProLinx Gateway
IEC-60870-5-104 (104S) Protocol Implementation
(Firmware v3.00 and later)
Protocol Manual
ProSoft Technology, Inc.
Page 71 of 157
January 22, 2010
Use the
Select/Operate Timeout
parameter to configure the select/operate timeout
period. After the gateway receives the SELECT command it will wait for this period
of time to receive the EXECUTE command for the same point address. If the
gateway does not receive an EXECUTE command within this period of time, it will
require another SELECT operation before the EXECUTE operation will be accepted
and acted upon.
3.4.2 Command
Points
Addressing
Command points must be configured in a database area that is updated in the
gateway memory database. You must associate each point to a database address in
the 104S gateway. The interpretation of the
DB address
parameter in the
configuration tables depends on the point type configured and the type of addressing
associated with that point type.
Data Type
Data Size
Addressing Type
C_SC_NA 1
bit
Bit
C_DC_NA 2
bits
Bit
C_RC_NA 1
byte
Byte
C_BO_NA 2
words
Double-word
C_SE_NA 1
word
Word
C_SE_NB 1
word
Word
C_SE_NC 2
words
Double-word