IEC-60870-5-104 (104S) Protocol Implementation
104S
♦
ProLinx Gateway
Protocol Manual
(Firmware v3.00 and later)
Page 76 of 157
ProSoft Technology, Inc.
January 22, 2010
C_BO_NA
A 32-bit Bitstring Command point occupies two words and uses double word
addressing.
For example, if you configured the following points:
These points would be used as follows:
Inf. Object Address
Module Database Address
3100
Words 3000 and 3001 (Double-word address 1500)
600
Words 2000 and 2001(Double-word address 1000. Must
match the configuration of point 600 in M_BO_NA.)
3101
Words 3002 and 3003 (Double-word address 1501)
601
Words 2002 and 2001 (Double-word address 1001. Must
match the configuraton of point 601 in M_BO_NA.)
3102
Words 3003 and 3004 (Double-word address 1502)
602
Words 2004 and 2005 (Double-word address 1002. Must
match the configuration of point 602 in M_BO_NA.)