IEC-60870-5-104 (104S) Protocol Implementation
104S
♦
ProLinx Gateway
Protocol Manual
(Firmware v3.00 and later)
Page 94 of 157
ProSoft Technology, Inc.
January 22, 2010
General (All Points)
You may control how frequently the gateway will scan the database for events using
the
Event Scan Delay
parameter:
If this parameter is set to 0, the gateway will not generate events for any points. A
non-zero value will configure how frequently the gateway scan for events in the
database.
Note:
Please note that setting this value too low (less than 50ms) will force the module to scan all
points for events at that rate. If set too low, overall module performance will suffer. For this reason, it is
generally suggested to use values greater than 50ms for
Event Scan Delay
.