5.0  Faults 

The ProPointPlus monitors various aspects of the unit to ensure the unit is fully operational. During faults the 
fault LED will illuminate and the buzzer will sound a slow pulse tone. Listed below are the diagnosed faults 
indicated on the unit. 

Table 1 System Faults 

Fault 

Description 

Action 

Device 
Missing 

A communication problem to a device within the unit 
has been detected or a device has been removed 
from the unit. 

Check the device in fault is fitted 
correctly otherwise contact a 
Protec operative or a Protec 
distributor. 

Device 
Added 

A new device has been added to the unit but the 
device has not been commissioned.

 

Contact a Protec operative or a 
Protec distributor. 

Airflow Fault 

The airflow measurement has moved outside the 
acceptable tolerance range either by an increase or 
decrease in normalised airflow.  

 

Check sampling pipe installation 
is correct as per commissioning, 
ensure no pipes are blocked. 
If fault persists contact a Protec 
operative or a Protec distributor. 

Supply Fault 

The supply fault monitoring input is reading low. 
Typically connected to the external power supply 
charger unit.

 

It may be necessary to look at the 
power supply charger unit to 
determine the cause of the fault. 
If fault persists contact a Protec 
operative or a Protec distributor. 

High Optical  

 

Background 

The optical value has increased outside the normal 
operation range.

 

Contact a Protec operative or a 
Protec distributor. 

Low  

 

Background 

The optical value has decreased outside the normal 
operation range.

 

Contact a Protec operative or a 
Protec distributor. 

Link Fault 

The data (RS485) path has failed.

 

Contact a Protec operative or a 
Protec distributor. 

Output 
Override 

The inputs ‘check to test’ option is active, activated 
using the ProView.exe PC software. 

Contact a Protec operative or a 
Protec distributor. 

Corrupt 
Settings 

Internal settings are outside the expected values. 
Unit will default to factory settings. 

Contact a Protec operative or a 
Protec distributor. 

Low Supply 

The supply voltage to the unit is below the operating 
value (<19V

DC

). 

Contact a Protec operative or a 
Protec distributor. 

Corrupt File 

Web server file is corrupt. 

Contact a Protec operative or a 
Protec distributor. 

Calibration 
Fault 

The SCD calibration offset value is out of limits. 

Contact a Protec operative or a 
Protec distributor. 

LED Fault 

The SCD optical LED is damaged. 

Contact a Protec operative or a 
Protec distributor. 

Airflow 
Ignored 

A pipe airflow is set to be ignored, activated using the 
ProView.exe PC software. 

Contact a Protec operative or a 
Protec distributor. 

CO Cell Fault 

The SCD Carbon Monoxide (CO) cell has expired its 
life capacity or is missing. 

Contact a Protec operative or a 
Protec distributor. 

Fan Fault 

The fan is damage or under/over performing. 

Contact a Protec operative or a 
Protec distributor. 

Isolated Fault 

Either the SCD(s) have been individually disabled or 
the isolate input is active. 

If used check external input 
isolation equipment. Otherwise 
contact a Protec operative or a 
Protec distributor. 

Heat Fault 

The heat thermistor reading is out of range. 

Contact a Protec operative or a 
Protec distributor. 

Incomplete

 

Manufacture 

The manufacturing details have not been stored in 
the unit. 

Contact a Protec operative or a 
Protec distributor. 

Fault (85) 

An incorrect SCD device fitted in the unit. 

Contact a Protec operative or a 
Protec distributor. 

 

Summary of Contents for ProPoint PLUS

Page 1: ...Protec Fire Detection plc Protec House Churchill Way Nelson Lancashire BB9 6RT ENGLAND 44 0 1282 717171 www protec co uk sales protec co uk PROPOINT PLUS ASPIRATING SMOKE DETECTION SYSTEM USER MANUAL ...

Page 2: ...N 93 602 00 Issue 1 Page 2 of 10 Protec Fire Detection PLC 2015 Document Revision Details Issue Modification Detail Author Date 01 Document Creation RB 15 11 2015 ...

Page 3: ...This equipment has been manufactured in conformance with the requirements of all applicable EU council directives and regulations Electrical or electronic devices that are no longer serviceable must be collected separately and sent for environmentally compatible recycling in accordance with the European Waste Electrical and Electronic Equipment Directive To dispose of old electrical or electronic ...

Page 4: ...plications ProPointPlus provides up to four separate detectors within a common aspirator enclosure and therefore provides four individually identifiable areas of detection per aspirator Each of the four plug in Scatter Camber Detectors SCD s detector use independent and integrated alarm decision making Complex algorithms are used to extend the range of particle detection confirm genuine alarms and...

Page 5: ...is in Fault Pre alarm or Fire providing the buzzer is enabled at commissioning The buzzer can be muted by pressing any button LED indicators are programmed to illuminate corresponding to a specific event The button functions are to navigate thought the commissioning menu and are therefore not a requirement for the user 4 1 Display Figure 4 1 ProPointPlus display detector normal Power LED Green Fir...

Page 6: ... in the centre of the display When more than one faults is reported the faults are automatically scrolled though each fault on the display The fault LED will be illuminated If the fault is pipe specific the pipe number is displayed in brackets next to the fault for example below shows 1 Airflow Fault describes an airflow fault on pipe 1 Figure 4 2 ProPointPlus displaying a fault condition Refer to...

Page 7: ...ipe 1 and Pipe 2 are in Pre Alarm condition Warning Pipe 3 and Pipe 4 are in Normal condition The Pre Alarm LED is illuminated any commissioned outputs will activate and the fire condition is reported to the Protec Fire panel Figure 4 3 ProPointPlus displaying Pre Alarm condition The appointed Responsible Person should investigate the relevant area following the official procedures for the buildin...

Page 8: ...presented as Fire The example picture below shows 4 pipes where Pipe 2 are in Fire condition Pipe 1 Pipe 3 and Pipe 4 are in Normal condition The Fire LED is illuminated any commissioned outputs will activate and the fire condition is reported to the Protec Fire panel Figure 4 4 ProPointPlus displaying Fire Alarm condition The building fire plan must be executed immediately Muting the buzzer The b...

Page 9: ...r a Protec distributor Link Fault The data RS485 path has failed Contact a Protec operative or a Protec distributor Output Override The inputs check to test option is active activated using the ProView exe PC software Contact a Protec operative or a Protec distributor Corrupt Settings Internal settings are outside the expected values Unit will default to factory settings Contact a Protec operative...

Page 10: ... LED Alarm Fire Red LED OLED Display Unit status Faults Pre Alarm and Fire and Commissioning menu Sensitivity A High B Enhanced C Normal Number sampling hole alternative to point type smoke detector Holes per pipe max Pre Alarm Level1 Fire Level1 A1 A2 A3 3 150 2 2 m 200 2 9 m B1 B2 B3 B4 B5 5 150 2 2 m 250 3 6 m C1 C2 C3 C4 C5 C6 C7 C8 8 150 2 2 m 250 3 6 m Prison 1 Max area coverage per pipe 800...