DISPLAY
OFF
CLOSING
PHOTOCELLS
OPENING
PHOTCELLS
PHOTOCELLS
TEST FAILED
EMERGENCY
STOP
START
COMMAND
PEDESTRIAN
START
COMMAND
MOTORS
TEST
FAILED
LIMIT SWITCHES
RADIO
5. TROUBLE-SHOOTING
Possible Reasons
Po
wer-cut
Burnt fuses
Tran
sformer problem
Misalignment of the photocells
Obstacle disturbing the
photocells beam
Incorrect wiring
Photoc
ell not powered
Clo
sing photocells not wired
Misalignment of the photocells
Obstacle disturbing the
photocells beam
Incorrect wiring
Ph
otocell not powered
Opening photocells not wired
Incorrect wiring
Unfitting photocells
Incorrect wiring
Emergency STOP push-button not
wired
The
control panel is receiving a
continuous START command
The
control panel is receiving a
continuous PEDESTRIAN START
command
Mo
tors not wired
Incorrect wiring
Electrical coil broken
Faulty limit switch
Lac
k in wirings
The control panel is continuously
receiving a radio command
Solutions
Check main power supply
Repl
ace the fuses
C
heck all connections and input/output voltage
Check transmitter and receiver position/alignment
Check and remove the obstacle. Also check the photocells eye and
remove any dust or dirty deposit.
Check all electrical wirings following the diagram
Check power and voltage both on receiving and transmitting
photocell
Wir
e the photocells or disabled corresponding parameter (please
refer to paragraph
3.6.1
)
Check transmitter and receiver position/alignment
Check and remove the obstacle.
Also check the photocells eye and remove any dust or dirty deposit
Check all electrical wirings following the diagram
Check power and voltage both on receiving and transmitting
photocell
Wire
the photocells or disable corresponding parameter (please refer
to paragraph
3.6.2
)
Check all electrical wirings following the diagram
Pleas
e install original photocells
Check all electrical wirings following the diagram (paragraph
3.5
)
Wire
the STOP push-button or disable corresponding parameter
(please see paragraph
3.5
)
Make sure that all START controls connect are properly working and
correctly wired (N.O. contact)
Make sure that all PEDESTRIAN START controls connect are properly
working and correctly wired (N.O. contact)
Wir
e the motors as shown in the diagram
Check motors electrical wiring (please see paragraph
3.3
)
Use a tester to check the coil status
Replace the limit switch
Heck wirings to control unit and limit switch
Check all keys of the remote controls.
Make sure that there is no stuck key (led on the remote control always on).
If needed remove the battery from the remote control and check
that the error message disappears from the display