background image

19

S-PARK

 - rev.1.1_06_2020

5.3.7  

U. Maintenance

 

U.1 Overall cycles performed

This feature allows to display the overall cycles performed. 

No possibility of reset.  

Cycles are displayed 2 by 2 figures: 

Ex.:

 if the barrier totally performed 823.605 cycles, the screen will 

read:

 

00. 82 36 0.5.

If you wish to scroll figures just press key 

 .

 

U.2 Cycles performed since last maintenance service

This feature allows to display the overall cycles performed since last 

maintenance service. 

Cycles can be reset when a maintenance service has been carried 

out (if U.3 is updated and set up). 

If you wish to reset press   and   together holding for 3 seconds: 

display will flash “

” to confirm reset successfully completed

 

P.4 LED signalling strip (optional)

Boom can be fitted with a RGB led strip that makes the operation more 

visible.

The LED strip can be adjusted in 4 different signalling modes when 

boom is in closing position. 

Refer to be below table:

P.4

Signalling mode when boom in closing position

0

OFF

1

Lit (red light); flashing if battery powered

2 (default) Lit (red light).

3

Flashing (red light)

 

P.5 Light sensor

It is possible to wire a light sensor or daily/weekly timer to switch 

the LED signalling strip OFF during day hours. 

There are two possible configurations:

 

• Wiring the N.O. contacts of the sensor/timer in series to COMMON 

(terminal BOOM+24)

 

• Wiring the N.O. contacts of the sensor/timer between GND 

and STRT2 or LD, setting

 P.5

 accordingly; in this case the wired 

terminal looses its original function.

P.5

Light sensor possible configurations

0 (default)

No light sensor is wired to STRT2 or LD. 

1

Light sensor is wired between STRT2 and COM. 

START2 no longer works as pedestrian contact. 

2

Light sensor is wired between LD and GND. 

 LD no longer works as Loop detector.

 

P.6 Cabinet’s safety switch

The barrier may develop extremely dangerous circumstances during 

operation. 

That’s why if cabinet is opened the barrier immediately stops working 

(just figure out if accidentally a radio start command is given, how 

dangerous it could be).  

However barrier can be managed in “dead man” mode using on 

board keys. 

P.6

 safety function may be switched OFF setting 

P.6

 to 0 position; by 

default 

P.6

 is 

ON (P.6=1)

.

 

U.3 Maintenance countdown

This feature allows to set the number of cycles till next maintenance 

service (starting from a minimum of 1000 cycles and so on). 

U.3

 will accordingly and automatically update 

U.1

 and 

U.2

 if activated, 

at every closing operation.   

It is also possible to warn the end user that maintenance service is 

needed. 

To set this function, set parameter 

U.4

.

 

U.4 Maintenance recall

As previously explained in parameter 

U.3

, it is possible to set a 

visible flashing “maintenance recall”. 

Refer to the below table to set the desired recall configuration:

P.3

LD output / features and contacts (N.O./N.C.) 

0 (default)

The contact is OFF.

1

N.O. (normally opened) START command. 

The closed contact makes the barrier opening.

2

N.O. SAFETY mode

The closed contact makes the barrier reverting exactly 

as a closing photocell.

3

N.C. (normally closed) START command
See setting 1 above.

N.C. (normally closed) SAFETY mode

See setting 2 above

U.4

Maintenance recall – signalling configuration

(default)

OFF – factory setting

No maintenance recall has been activated. 

1

SPECIAL FLASHING DURING AUTOMATIC CLOSING TIME

When boom in vertical position, the flashing light on the cabinet 

permanently flashes. 

To activate this mode the automatic closing time shall be set 

no less than a couple of seconds, otherwise signalling will not 

be sufficiently visible

.

2

SPECIAL FLASHING DURING OPENING

When boom is opening, the flashing light on the cabinet 

permanently flashes.

3

AUX OUTPUT

AUX output activates (the contact closes) when maintenance 

service is neeed.

 

P.3 LD loop detector

P.3 allows to fit to LD terminal a vehicle detector (loop detector) that 

works exactly as a safety device, like closing photocell. 

In addition it can command a START pulse: when the vehicle 

approaches the barrier, a START command is given and the barrier 

opens.

Settings available:

Summary of Contents for S-Park 4

Page 1: ...1 S PARK rev 1 1_06_2020 S PARK AUTOMATIC ROAD BARRIER User manual ...

Page 2: ... 11 3 7 Wirings 11 3 7 1 Main power 230V 11 3 7 2 Back up batteries 11 3 7 3 Stand alone antenna optional 12 3 7 4 Wiring diagram 12 3 8 Legenda of terminals 13 3 8 1 START wired command contacts key switch key pad timer 13 3 8 2 STOP emergency push button or similar devices 13 3 8 3 STRT2 optional additional START contact 13 3 8 4 PH Closing photocell N C dry contact 13 3 8 5 24 SAFETY Closing ph...

Page 3: ...inker 18 H 3 Follow me closing 18 H 4 Automatic closing after power cut 18 H 6 Master slave barrier configuration 18 5 3 5 L WORKING TIMES 18 L 1 Automatic closing 18 L 2 Automatic closing pedestrian opening 18 5 3 6 P SAFETY 18 P 1 STOP 18 P 2 PH closing photocell 18 P 3 LD loop detector 19 P 4 LED signalling strip optional 19 P 5 Light sensor 19 P 6 Cabinet s safety switch 19 5 3 7 U MAINTENANCE...

Page 4: ...ting from page 21 Proteco S r l reserves the right to make changes to the product without notice Main power Max absorption Motor power Accessories Torque Opening time Operating temperature Duty cycle IP rating 2 TECHNICAL FEATURES 2 1 Main features 230V 50 60 Hz 230V 50 60 Hz 1 2A 230V 1 2A 230V 24V dc 24V dc 24V dc 24V dc 120 Nm 180 Nm 2 5 4 sec 4 5 6 sec 25 C 55 C 25 C 55 C 80 80 max 200 cycles ...

Page 5: ...EN ANTENNA KEY KEY KEY KEY START commands START START2 pedestrian opening STOP Radio 433 MHz embedded radio receiver storage up to 96 random o rolling codes Safety devices Closing photocell loop detector configurable Additional appliances TWINNING mirror barriers timer light sensor Outputs RGB led signalling strip AUX output Optional interfaces Expansion connector for optional modules Connector fo...

Page 6: ...the barrier area has been left While the boom length can be adjusted the concrete basement remains fixed as it is built Picture 2 Boom from 4000 to 6000 mm Picture 2 Overall layout 3 4 Basement preparation It is absolutely key to build a solid concrete basement at least EN206 C25 30 proof Basement dimensions must be no less than 400x500mm and no less than 600mm deep We recommend to consider an ext...

Page 7: ...e barrier hand is determined proceed to fit the spring accordingly as shown in the above picture If you need to change the opening orientation complete the installation first and then follow the instructions rotating to 90 the equalizer lever before repositioning the boom and spring ATTENTION FOR SAFETY REASONS REMOVE THE BOOM JUST WHEN IN VERTICAL POSITION 3 6 2 Mounting of the boom After determi...

Page 8: ...ARTMENT AS SHOWN IN PICTURE 14 Picture 14 3 6 3 Manual operation In order to facilitate adjustments balancing spring and limit switch regulation put the barrier in manual operation mode Put the barrier to manual operation mode just after completing the whole installation Be carefull when releasing the boom it could accidentally lift up and be dangerous Use the lock located on the right side of the...

Page 9: ...nd put the boom to vertical position Lock it again Drive the M12 hexagonal screw through the spring hole and put a washer as spacer The screw s head must be oriented as shows Picture 18 Fit the spring to the equalizer lever using the proper hole Put a washer in order to facilitate rotation Tighten bolt and washer M12 Use the hook to secure the spring to barrier s plate as shows Picture 19 ATTENTIO...

Page 10: ... of the barrier during operation Drive the LED strip through the proper compartment inside the rubber profile LED lights have to be downward oriented refer to Picture 25 Picture 25 LED downward Picture 21 For a proper balancing adjust the tension of the spring rotate the spring anticlockwise to decrease the tension rotate the spring clockwise to increase the tension Move the boom manually to 30 po...

Page 11: ...led on the same drive way as shows the above picture can work simultaneously if wired together on TWIN terminals The master barrier will command the slave barrier slave barrier may only stop if detecting an obstacle during operation Any safety and command devices shall be wired to the master barrier only As well the master barrier is the only one that shall perform pede strian opening terminal STA...

Page 12: ...al stand alone atenna remove the Whip aerial and wire the core cable RG58 wire the shield cable on the other terminal as shown in the picture SHIELD CORE 3 7 4 Wiring diagram The below diagram is a mere overall view about all possible wirings AUX TWIN SLAVE BARRIER LED STRIP LOOP DETECTOR NO or NC contact TRANSMITTER RECEIVER INFRARED BEAM ...

Page 13: ...g photocell test 3 8 6 TX Closing photocell cuts power during photocell test This terminal powers at 24Vdc 0 3A all safety devices but unlike 24 SAFETY cuts the power during photocell test 3 8 7 LD Loop Detector This terminal can manage both N O and N C contacts loop detector works as closing photocells do but in addition can also command an opening start pulse Wire the loop detector between LD an...

Page 14: ...he display is in stand by _ _ OPENING MODE The blinker flashes slowly and the display shows opening If during opening the barrier detects an obstacle the boom reverts to closing position remains still for 10 seconds the display shows count down and then starts to open again AUTOMATIC CLOSING COUNTDOWN When countdown begins the blinker starts flashing briefly for a few seconds switiching then to fi...

Page 15: ...y quits the programming and returns to operation mode 5 PROGRAMMING 5 1 Settings configuration Proceed to programming only when the barrier is in still mode any key pressed during operation stops the barrier Press key and hold shortly a quick pulse is insufficient display reads A 1 Press as many times as finding the desired parameter expressed by an alphabetical letter left side of the display The...

Page 16: ...ption 5 3 1 A RADIO This menu includes procedures about how to store radio devices remote controls mainly Every remote control stored is automatically identified by a progressive number if by accident a remote control is lost it can be deleted from the control unit memory It is possible to store up to 96 different users when a remote control is deleted its radio position still remains available fo...

Page 17: ...sition therefore the signalling light may remain switched off 5 COURTESY LIGHT 30 the output is activated when the contact closes and remains closed during the whole working cycle The contact opens after 30 seconds after working cycle is completed 6 COURTESY LIGHT 60 the output is activated when the contact closes and remains closed during the whole working cycle The contact opens after 60 seconds...

Page 18: ...INNING OFF 1 Set 1 to configurate the master barrier 2 Set 2 to configurate the slave barrier 5 3 5 L Working times L 1 Automatic closing This parameter sets the automatic closing time adjustable from 0 automatic closing OFF to 99 seconds L 2 Automatic closing pedestrian opening This parameter sets the automatic closing time for pedestrian opening adjustable from 0 automatic closing OFF to 99 seco...

Page 19: ...mmediately stops working just figure out if accidentally a radio start command is given how dangerous it could be However barrier can be managed in dead man mode using on board keys P 6 safety function may be switched OFF setting P 6 to 0 position by default P 6 is ON P 6 1 U 3 Maintenance countdown This feature allows to set the number of cycles till next maintenance service starting from a minim...

Page 20: ...version ex 1 0 or 2 3 and similars If control unit is brand new and no programming has been carried out yet the display reads EE for a half second As last step control unit goes to STAND BY mode and display reads flashing The remaining messages are listed in the below table 6 1 Messages During normal operation messages may show up Refer to the below table indicating possible messages and according...

Page 21: ...8 END USER S TIPS Dear user it is highly recommended to read the following pages because they may contain essential information for the safety of people and things and in compliance with applicable laws Store these pages in a safe place for future reference 8 1 Warnings Keep the system away from children under 8 Children and People with reduced physical sensory mental or limited experience and or ...

Page 22: ... 8 3 Maintenance In order to preserve the proper performance and safety of the barrier over time it is highly recommended to schedule a regular maintenance plan with your installer and report any uncommon behaviors that may require inspection In case of malfunctions it is wise to contact the installer who installed the barrier rather than others End user may just keep clean photocells and the barr...

Page 23: ...arrier automation Models S PARK 4 S PARK 6 Is built to be integrated into a machine or to be assembled with other machinery to crate a machine under provisions of 2006 42 EC Machinery Directive It complies with the essential requirements of EEC Directives 2014 30 UE EMC 2014 35 UE LVD 2014 53 UE RED 2011 65 CE RoHS2 The product also complies with EN 60335 1 and EN 60335 2 103 standards The manufac...

Page 24: ...24 S PARK rev 1 1_06_2020 Proteco S r l Via Neive 77 12050 CASTAGNITO CN ITALY Tel 39 0173 210111 Fax 39 0173 210199 info proteco net www proteco net ...

Reviews:

Related manuals for S-Park 4