35
R
EMOTE OPERATION VIA
WEB BROWSER
E Operating Manual with Troubleshooting Guide
www.protecta.hu
4.2.10.4 Update manager
In the
Restore
field the user can upload configuration and parameter settings from a
report.zip
file into the device.
Device firmware can be upgraded when a new version is available. Information about the current
RDSP/CDSP firmware
and for the downloaded configuration file can be found in the text fields
To update, click on the Update button, select the appropriate file and click OK. A dialog on the
LCD will ask you to confirm updating. Detailed information about the latest firmware updates can
be found on the Protecta website in the
firmware update is needed, please contact Protecta
All digital outputs (relay contacts, trip contacts) must be disconnected from the protected object(s)
before commencing firmware update.
Caution! Never load an older version of the firmware to the device!
Firmware update must always
be done with care, because mistakes in this process may cause devices malfunction!
It is advised to get the system state report of the device (
report.zip
) before commencing the
update. This way the device will be able to be restored if something goes wrong.
In the
Configuration
field the user can download the configuration file (.epc) from the device.
Figure 4-32 Update manager