----------- PROXEL ENGINEERING -------------------- www.proxel-bg.com------------------------------ DTLED rev. 1.6/06.2015------
5
TECHNICAL DATA
Power supply: 230V±10% /50Hz. ≤ 2VА
Instalation on DIN rail 35mm; to be incorporated
Enviroment: -25T45, RH80%
Storage and transportation -30/+60 º C
Overall dimentions 68x85x58 mm.
Protection casing IP20
Sensors: durability 200 ºC
Measurment and display: -40ºC÷199 ºC;
Accuracy ±1ºC in range (-5ºC ÷ +100 ºC);
±4ºC not in range
Outputs:
-Relay R1 - 220V - 5A or 180W/AC3 (motor)
-Relay R2 -
220V - 5А or
180W/AC3 (motor)
Two independent relay contacts!
Instalation and commusioning
This device is designed to be incorporated in apartment electrical box with size of 4 or more poles or a cabinet and
can be attached on 35mm DIN rail. Assembly outside of the board is unacceptable.
Initial setup routine:
1.
Turn off the power supply
2.
Open the top of the body of the product by pushing the locking tabs on both sides of the
base.
3.
Adjust the basic parameters according to the enclosed instruction.
4.
Place the top cover until it is fully attached to the base
Attention!
Danger of electric shock!
All activities involving installation and commissioning should be done while electric power is off
.
Attention! To control tank’s heater it is necessarys to add an external commutator
(powerfull relay) controlled by the thermostat’s output and to keep all the protective
and switching elements provided by the tank manufacturer (switch, thermostat,
thermal protection)!
DTLED is not a protective device within the meaning of EN60730-1-Annex
Attention!
The supply of the "Phase-La"
power supply to the device is
carried out through a fuse:
Class B 6A max. on terminals
no. 21 and no. 16
----------- PROXEL ENGINEERING -------------------- www.proxel-bg.com------------------------------ DTLED rev. 1.6/06.2015------
6
WARRANTY THERMS AND CONDITIONS:
The warranty period of the product is 24 months from the day of sale or installation by the installer but no more
than 30 months from the date of manufacture. The warranty covers defects attributable to the manufacturer
(manufacturing defects or defective materials). They are not subject to warranty defects in the product or damage to
other equipment as a result of improper or unskilled installation, improper workflow selection and / or adjustment,
unauthorized change of the product, natural disasters, non-standard power supply, improper storage or
transportation.
Тук гаранционна карта на английски прилага ли се???????
Table for diagnostic of temperature inputs
Temperature-resistance-voltage table of sensor inputs KTY81-1К
TºC
-40
-35
-30
-25
-20
-15
-10
-5
0
5
10
15
20
R -[
Ω
]
567
602
624
653
684
714
747
780
815
849
886
922
961
Uвх-[V]
1.37 1.43 1.47 1.52 1.57 1.61 1.66 1.71 1.76 1.81 1.86 1.90 1.95
TºC
25
30
35
40
45
50
55
60
65
70
75
80
85
R- [
Ω
] 1000 1040 1081 1122 1165 1209 1254 1299 1346 1392 1441 1490 1541
Uвх-[V]
2.00 2.05 2.09 2.14 2.19 2.23 2.28 2.32 2.36 2.41 2.45 2.49 2.53
TºC
90
95
100
105
110
115
120
125
130
135
140
145
150
R- [
Ω
]
1591 1643 1696 1750 1806 1861 1915 1970 2023 2075 2124 2172 2211
Uвх-[V]
2.57 2.61 2.65 2.69 2.73 2.77 2.80 2.84 2.87 2.90 2.93 2.96 2.98
Warranty card
Please completely fill this card for valid guarantee
Manufacturer: Proxel Engineering Ltd Type: Temperature controller DTLED
Plovdiv, Bulgaria, office@proxel-bg.com
Serial number: Data of manufacture:
............................. .................................
Seller/Installer:.............................................................................................................................
.
Address: ........................................................................................................................................
Date of (sale) Instalation: .........................................................................................
Installer/ seller :.........................................................................................................
(name and signature )
Instalation is made by
Installer
Client
(please mark the true one)
2004/108/EC
200
6
/
95
/EC