14
Change Timing
Options Y/N
Min Run Time 2
Minutes U/D/Next
Min Off Time 2
Minutes U/D/Next
Press Up or Down to set the
number of minutes a heating or
cooling call must run. Press
NEXT to continue.
Press Up or Down to set the
number of minutes a heating or
cooling call must be off before
another call is started. Press
NEXT to continue.
Press Yes to change the minimum
run and off times or press No to
continue.
Display Data And
Settings Y/N
Start Panel Test
Y/N
Start Dmpr Test
Y/N
Start Cooling
Test Y/N
Cooling Stg1 On
DA Temp 56 Next
Start Htg Test
Y/N
Heating Stg1 On
DATemp 110 NEXT
Start Bypass
Test Y/N
All Dampers Open
Cooling On Next
Damper 1 Open
Clg On U/D/NEXT
Damper 1 100%
Clg On U/D/NEXT
Damper 2 Closed
Clg On U/D/NEXT
Damper 2 Closed
Clg On U/D/NEXT
All Dampers Open
NEXT
Damper 1 Closed
NEXT
Damper 2 Closed
NEXT
Press Yes to display all the option
settings, sensor data, call status, error
messages and much more. This option
only displays settings and data. No
setting can be changed. Press No to
continue.
Press Yes to start a test of damper
operation, cooling system and the
heating system.
Press Yes to start a test of the
dampers to insure they are opening
and closing.
Press Yes to start a test of the
cooling system to insure discharge
temperature is correct
Press Next to test stage2 cooling or
start a heating test (if only 1 cooling
stage).
Press Yes to start a test of the
heating system to insure discharge
temperature is correct.
Press Next to start a test stage2
heating to insure discharge
temperature is correct or return to
the main menu if only one stage of
heating is used.
Press Yes to start a bypass test. A
test will be started based on the type
of bypass being used.
Press Next to select which dampers
are open and closed.
Press the Up and Down keys to
open or close a damper. Press the
Next key to change the next damper.
To test various bypass settings, use
the Up and Down keys to set the
position of each zone damper. Fully
open is 100% and fully closed is 0%.
Press Next to set the next damper.
After setting the position of each
damper, press the Save key to have
the panel position the dampers.
Check the airflow in both calling
zones and non-calling zones to
insure the airflow is acceptable.
Press the Cancel key to cancel the
test and return to the main menu.
Press the Up and Down keys to
open or close a damper. Press the
Next key to change the next damper.
After setting the dampers to open
and close, press the Save key to
have the panel position the
dampers.
Adjust the barometric damper and
check that the airflow to the non-
calling zones is low enough.
Press Cancel to end the test and
return to the main menu.
All the dampers open and the fan is
activated. Check that you have air
from the registers in all zones. Press
Next to continue.
Damper1 closes. Check that there
is no air from the registers in Zone1.
Press Next to continue.
Damper1 opens and Damper2
closes. Check that there is no air
from the registers in Zone2. Press
Next to continue to test each zone
damper.
Testing the Installation
Bypass Testing
Bypass Testing with External Barometric Damper
Bypass Testing Modulating the
Non-Calling Zone Dampers