background image

Factory Settings

Gas/Electric

20 minutes

60 seconds

ProR80J-XX

Heating

2 minutes

2 minutes

Off

Gas

o

160 F

o

45 F

Zone1

External Barometric

Equal

Off

Off

Weighted Zones

o

55 F

On

Off

Gas/Electric, conventional or dual fuel heat pumps.

o

40 to 60 F. Requires outdoor temperature sensor.

External Barometric or adjusting damper close position. .

Selections

Options and Factory Settings, All Zoning Panels

30 to 240 seconds.

Equal or different.

5 to 240 minutes.

Heating or cooling.

0 to 10 minutes.

0 to 10 minutes.

On or Off.

Gas or electric.

Weighted Zones calling.

o

110 to 180 F

o

37 to 55 F

ProR80J-XX

On or Off

On or Off.

On or Off.

On or Off

Zone1.

Opposite System Service

Moderate Weather Limit

Moderate Weather Temp

Opposite System Time

Staging Calculations

Minimum Run Time

Minimum Off Time

Fresh Air Control

Indoor Fan Mode

Em Heat Control

Timed Upstaging 

High DAT Limit

Low DAT Limit

Dampers Used

Purge After Call

Priority System

Zone Sizes

Purge Time

Equipment

Bypass 

Option

Select Equipment
By Clone     Y/N

Change Equipment
Options      Y/N

Change Zone Size
             Y/N

Change Tstat
Options      Y/N

Installer Menu

Press and hold the MENU key for 4 seconds to access the 
Installer menu.   The PDMi3 displays “Waiting for Data” while it 
reads the panel settings.  The MAIN menus are shown below.

Press Yes to use a previously saved 
configuration to clone this panel to the 
same settings.  Press No to continue.

Press Yes to set the number of stages of 
heating and cooling, the fan operation, 
the supply air temperature limits, outdoor 
changeover temperature for dual fuel 
heat pumps and number of zones being 
used.  Press No to continue. 

Press Yes to change the size of each 
zone. The zone size is set in a weighted 
value from 0.5 to 2.0.  A small zone might 
be 0.5 and a large zone might be 1.5 
zones. Be sure the total is equal to the 
total number of zones. Press No to 
continue. 

Press Yes to change the type of 
thermostats used.  When heat pump 
equipment is selected, the Zone1 
thermostat may be a  heat/cool or heat 
pump type and the reversing valve 
operation (O or B) can be selected. 

Change Staging
Options      Y/N

Change Bypass
Options      Y/N

Press Yes to change the staging using 
the weighted zones calling and the timer.  
Each stage can be set to turn on at the 
same or different weighted zones calling 
at the time.  Or a stage can be delayed 
and set to turn on after the call has been 
active for a number of minutes.

The delayed option can be used to meet 
the new Title24 requirement to delay 
auxiliary strip heating in a conventional 
heat pump.

Timers can be set to override capacity 
staging and activate each stage after the 
call time has reached a number of 
minutes.  Press No to continue. 

Press Yes to change the bypass options.  
Bypass can be achieved using the non-
calling zone dampers, using the Close 
stop position or a bypass duct between 
the supply and return controlled by a 
barometric damper.  Press No for other 
menu selections.

8

See page 10 for more information.

See page 10 for more information.

See page 11 for more information.

See page 10 for more information.

See page 9 for more information.

Summary of Contents for ProR212J

Page 1: ...nfigure a zone All panels operate with gas electric systems conventional heat pumps and dual fuel heat pumps Selected using the jumper plugs on the panel See table below See table below See table belo...

Page 2: ...ir damper is open LEDs indicate zone damper position Multi color LEDs indicate equipment call status Jumper plugs for selecting type of equipment Multi color LEDs indicate zoning panel status Terminal...

Page 3: ...n below 1 3 HVAC PANEL ZONE DAMPERS 1 1 2 2 3 FAD 3 THERMOSTATS Quick View ProR321J Zoning Panel ProZone Two 8 screws Two 8 screws Panel 3 Zone Maximum VA 40VA Transformer 60VA Transformer 75VA Transf...

Page 4: ...VAC Thermostat R C Y or Y1 G Zoning Panel R C 24VAC 24VAC Common Cooling Stage1 Indoor Fan Y G Terminal Function W1 OB Stage1 Heating W1 OB Inside Day Th MODE MENU FAN SYSTEM Schedule Auto Heat Heat S...

Page 5: ...AC EQUIPMENT W2 E Y2 R R O O B W1 B W Y Y1 Wiring HVAC Equipment Gas Electric System Two Stage Heat Gas Electric System Two Stage Cool Gas Electric systems using a single 24VAC transformer are wired a...

Page 6: ...ature Sensor Input Outdoor Temperature Sensor Input From Outdoor Temperature Sensor TS3 Terminal Function Discharge Air Temperature Sensor Model TS2 The optional discharge or leaving air temperature s...

Page 7: ...nd releasing the MENU key accesses the User menu where settings and data can be viewed but not changed 9 EXT PDMi MENU MENU NEXT NEXT SAVE SAVE PDM Programming Display Module PDM Programming Display M...

Page 8: ...and cooling the fan operation the supply air temperature limits outdoor changeover temperature for dual fuel heat pumps and number of zones being used Press No to continue Press Yes to change the siz...

Page 9: ...ing control The equipment type is set by the jumper plugs and cannot be changed with PDMi3 Press Yes to continue to select additional options Press Yes to select conventional heat pump If equipment ty...

Page 10: ...ats that can be used in that zone Press Up or Down to change the number of auxiliary heating stages Press NEXT to continue Press Up or Down to change the heating temperature limit Press NEXT to contin...

Page 11: ...he bypass position of the damper when it is being used for bypass Press Next to set the bypass position of the next damper Press Up or Down to adjust the bypass position of the damper when it is being...

Page 12: ...s NEXT to continue Press Yes to enter the minutes of fresh air operation required each hour Press No to select calculating the CFM and minutes per hour Press Yes to change the Fresh Air Option Press n...

Page 13: ...pposite system service The panel normally services heating or cooling calls based on the number of calls from the zones If there are more heating calls than cooling it will service heating and vice ve...

Page 14: ...t a test stage2 heating to insure discharge temperature is correct or return to the main menu if only one stage of heating is used Press Yes to start a bypass test A test will be started based on the...

Page 15: ...Press NEXT to go to the next letter in the name Press SAVE to save the clone name Monitor HVAC Performance Y N LAT 122 Prs 0 55 BP Pos 0 NEXT Press Yes to display the leaving air temperature duct pres...

Page 16: ...una Hills CA 92653 949 916 0945 Fax 949 458 8502 www ProZone US com Limited 5 Year Warranty The 5 year warranty is limited to the repair or replacement of defective product due to parts failure or def...

Reviews: