14
H- THERMOSTAT
The thermostat must be installed on an inside wall in a location where it is not likely to be affected by the draft
coming from an air outlet. It must be installed at a minimum of 55 inches above the floor.
N.B. Both thermostats on the combined wood / electric model must be installed at same height.
I- FAN CONTROL
The fan control setting varies depending on the type of installation. The setting “out of service” is preset at 110
o
F
at the factory. This setting should provide a proper operation for most installations. The temperature “in service” is
factory set at 150
o
F.
It is preferable for a prolonged operation of the blower that the setting “out of service” be low enough. But a
setting “out of service” too low will cause undesirable cold air circulation. To modify the setting, move the tab to the
desired position on the temperature dial of the fan limit control.
The adjustment of all controls must be performed by a qualified technician. The controls setting and the blower
speed must conform to the recommendations of the “Warm Air Heating and Air Conditioning National Association”.
The summer switch located on the electric unit controls the low speed either at the “on” or the “off” position. For a
quieter operation, it is recommended to use low speed for continuous operation of the blower (summer) and to leave
the high speed on automatic (wood side fan limit control) during the heating season.
OUTSIDE VIEW OF THE ELECTRIC ELEMENT