PTC-0110BA2UM, REV(A)

7

6.

Operation, Controls and Indicators   (ref. Figures 3 and 4)

6.1

Turning the UPS ON and OFF

In order to turn the UPS ON (after the electrical connections are made), turn ON the Input ON/OFF

switch (4), the Master ON/OFF switch (5) and if used, the remote ON/OFF switch. (The order is not

important). If remote ON/OFF is not used, the connections of J5 (described in paragraph 8.3)

should be installed before the unit is turned on.

When the Master ON/OFF switch  (5) or the remote ON/OFF switch are turned off, the internal

contactors open and disconnect both the input and the output of the UPS and it turns OFF.

When the UPS operates, turning off the Input ON/OFF switch (4) disconnects the UPS from the AC

input, and the UPS then runs on battery power only.

To turn the UPS off, the Master ON/OFF switch or the remote ON/OFF switch must be in the OFF

position. (It will automatically disconnect the input connector too).

Note:  The UPS will not start on battery power (to avoid battery discharge during shipping and

storage).  Hence, the Input ON/OFF switch must be ON and AC voltage must be present at the input

in order to start the UPS.

When a remote control of the UPS is desired, the Input ON/OFF and the Master ON/OFF switches

on the front panel should be both in the ON position. Turning the remote ON/OFF switch ON and

OFF will turn the UPS ON and OFF. (Please see paragraph 8.3).

6.2

Visual Indicators

6.2.1 Normal Operation

When the UPS is running on AC input power and both Master and Input switches are ON, the two

bar graphs (17, 18), the green Input OK LED (7) and the green Output OK LED (9) are on.

The Load Level Bar Graph (17) indicates the loading percentage of the UPS.  100% load is equal to

1000W of output power.  The lower six positions of the Load Level Bar Graph (15% to 75%) are

green.  The next three positions (80%, 110%, 120%) are orange and the two uppermost positions

(130% and 140%) are red.  The colors do not have any special significance and are only intended to

assist fast scanning of the load level.

The Battery Charge Bar Graph (18) indicates the percentage charge level of the battery.  100%

signifies that at least 10 minutes of full load will be supported by the battery, 50% signifies

5 minutes at full load and so on. Lower loads result in longer expected battery operation time.

When the battery is being charged, the uppermost active segment of the Battery Charge Bar Graph

blinks to indicate that charging is on.

6.2.2 Standby Mode

When the yellow Output Standby LED (8) is on, the UPS is in the Standby Mode. In this Mode the

DC-AC inverter is OFF and the output contactor is open, but all other function of the UPS are active

(including battery charging and RS-232 communication port). The UPS reaches this mode when

command by the RS-232 or the “dry relays” into this mode.

Summary of Contents for PTC-0110BA-2

Page 1: ...g Company AG UNINTERRUPTIBLE POWER SYSTEM 400Hz IN 60Hz OUT SINGLE PHASE 1kW 2kVA PTC 0110BA 2 MADE IN THE U S A USER S MANUAL P T C Production Trading Co AG P O Box CH 6330 Cham Switzerland Phone 41...

Page 2: ...8 6 3 Battery Test 9 7 Taking Care of the Battery 9 7 1 Battery Service Life 9 7 2 Replacing the Battery Pack 10 8 Communications and Remote Control 11 8 1 Dry Contacts Interface 11 8 1 1 Option 0 St...

Page 3: ...do not turn off the UPS The unit should only be plugged into an approved double pole and fused 20A electrical outlet The Replaceable Battery Pack of the 37 110BA 2 P N M357380 contains lead acid batte...

Page 4: ...microcontroller based Control Circuit The AC DC Converter is a high frequency switching converter that provides 320VDC to the DC AC inverter The AC DC converter draws clean sine input current waveform...

Page 5: ...ILTER VARISTOR AC DC CONVERTER DC AC INVERTER CONTROL MONITOR BATTERY CHARGER BATTERY PACK 24VDC 24VRTN INPUT ON OFF SWITCH MASTER ON OFF SWITCH REMOTE ON OFF SWITCH 2 POLES INPUT CONTACTOR 2 POLES OU...

Page 6: ...1 is the input connector J2 is the output of the UPS Figure 2 below shows the electrical power connections of the 37 110BA 2 After the unit is installed and ready to be turned ON see paragraph 6 1 Tur...

Page 7: ...ts See Figure 3 1 Removable air filter of the Power Conditioner s cooling air 2 Visual Indicators and Switches for detailed view see Figure 4 3 Air Inlet of main UPS heatsink 4 Input ON OFF Switch 5 M...

Page 8: ...ellow 12 Alarm Off Push button 13 Low Battery Warning LED blinking yellow 14 Overload Shutdown LED red 15 Overtemperature Warning LED blinking yellow 16 Overtemperature Shutdown LED red 17 Load Level...

Page 9: ...sition Turning the remote ON OFF switch ON and OFF will turn the UPS ON and OFF Please see paragraph 8 3 6 2 Visual Indicators 6 2 1 Normal Operation When the UPS is running on AC input power and both...

Page 10: ...sition Turning the remote ON OFF switch ON and OFF will turn the UPS ON and OFF Please see paragraph 8 3 6 2 Visual Indicators 6 2 1 Normal Operation When the UPS is running on AC input power and both...

Page 11: ...do not turn off the UPS The unit should only be plugged into an approved double pole and fused 20A electrical outlet The Replaceable Battery Pack of the 37 110BA 2 P N M357380 contains lead acid batte...

Page 12: ...ertheless it is a Limited Life Item and its life expectancy depends upon its operating and storage conditions The three most important factors that determine the life of the battery are Temperature St...

Page 13: ...ector access cover Remove screws e Disconnect the connector by pulling upward f Unscrew the right battery s screws on the top and three screws on the right side of the UPS marked by a B on the top and...

Page 14: ...O Not Battery Operation 3 5 System Common Ground 6 N C 7 O Battery Voltage Low 4 8 O UPS On 5 9 O Input Power Loss Battery operation 3 Notes to Table 1 1 Pin 1 is shorted to pin 2 when any one of the...

Page 15: ...9 N C Notes to Table 2 1 Connecting 5 to 12Vdc to pin 6 to pin 1 causes the UPS to shutdown if in Battery Mode latched 2 If AC input is good pin 7 is shorted to pin 2 and pin 3 is open If AC input is...

Page 16: ...lly shorted to J3 pin 9 not used by RS232 link 8 3 Remote ON OFF Interface J5 Important note The PTC 0110BA 2 is shipped with a matting connector plugged into J5 with a jumper that enables the unit If...

Page 17: ...cy Waveform 115Vac 3 grounded neutral see Note 1 2000VA 1000W 60Hz 0 2 digitally synthesized from a crystal oscillator Sinusoidal THD 2 linear load 4 non linear BATTERY Type Capacity Charger Protectio...

Page 18: ...us lamps Input OK and Input Fail status lamps On Batt status lamp Batt Passed and Batt Failed lamps for battery self test Low Batt warning lamp Overload Shutdown status lamp Overtemp warning and Overt...

Page 19: ...vel Charge Level status of all User Programmable Options and failure diagnostic Commands UPS Shutdown UPS Standby Initiate Battery Test Enable Disable Periodic Battery Test Enable Disable Battle Mode...