37&3URGXFWLRQ 7UDGLQJ&R$*
PTC-0110BA2UM, REV(A)
14
9.
Specifications
INPUT
Voltage
Frequency
Power Factor
Spikes
Isolation
Current
waveform
Line
impedance
85-140 VAC without switching to battery power.
(below this level the battery will be used).
360-440 Hz
> 92%
200 joules clamping device
Input is galvanically isolated from output and chassis (> 1 M
Ω
at 600VDC).
Total capacitance between input and chassis is less than 0.02uf per line.
Leakage current is less than 6ma.
Both input wires may be “hot” I.A.W. MIL-STD-1399.
Sinusoidal, with very low harmonic content I.A.W. MIL-STD-1399 section
300A.
Up to 5 ohms between 800Hz and 200kHz (I.A.W. MIL-STD-1399 section
300A.)
OUTPUT
Voltage
Rating
Frequency
Waveform
115Vac
±
3% , grounded neutral (see Note 1)
2000VA, 1000W
60Hz
±
0.2% (digitally synthesized from a crystal oscillator)
Sinusoidal , THD < 2% (linear load), < 4% (non-linear)
BATTERY
Type
Capacity
Charger
Protection
Monitor
Internal, encapsulated, sealed, maintenance-free, lead-acid.
Full rated power for at least 10 minutes.
Low ripple, regulated voltage float-charger, with current limiting and
temperature compensation. Fully charges the battery within 3 hours (following
10 minutes discharge at full power).
Battery is protected from over-discharge by internal protection circuit (to avoid
damage to battery in case of prolonged power outage.)
Battery charge level and internal impedance are monitored by the UPS micro-
controller.
EMC
Federal
Military
ESD
Meets the requirements of:
FCC Title 47 , part 15, class A.
MIL-STD-461D, RE101, RE102, CE101, CE102, CS101 and RS103.
All I/O lines are protected from ESD.