37&3URGXFWLRQ 7UDGLQJ&R$*
PTC-0110BA2UM, REV(A)
15
9. Specifications (continued)
ENVIRONMENT
Temperature
Humidity
Altitude
Orientation
Mechanical
shock
Vibration
Non operating: -40 to +72
°
C
Note: High temperature for prolonged duration will shorten the battery life.
Operating: 0 to +52
°
C.
Up to 95%. Over-sized, drip-proof front panel.
Operating: Up to 10,000 feet.
Non-operating: (Air transport) 40,000 feet.
May be installed at any orientation.
When packed, withstands the free fall drop and edgewise drop IAW
Methods 5007.1 and 5008.1 of Federal Test Method standard 101C.
When operating, withstands the high-impact shipboard shock IAW
MIL-S-901D, grade A, class II., Type B.
When operating, withstands Type I vibration IAW MIL-STD-167-1. The
UPS will endure a sweep of 1.5g sinusoidal vibration from 5 to 50 Hz for a
total duration of 2 hours, and random vibration IAW MIL-STD-810D, Cat.
9, Proc. I (test condition I-3.2.11, Fig. 514.3-34)
INDICATIONS
& CONTROLS
a) Visual
Indications
(Front panel)
b) Test Mode
c) Audible
Alarm
d) Power
Switches
e) Remote
ON/OFF
10-segment tri-color Bar Graph for load level display.
10-segment Bar Graph for battery charge level display.
"Output OK", "Output Fail" and “Standby” status lamps.
"Input OK" and "Input Fail" status lamps.
"On Batt " status lamp.
"Batt Passed" and "Batt Failed" lamps for battery self-test.
"Low Batt" warning lamp.
"Overload Shutdown" status lamp.
"Overtemp warning" and "Overtemp Shutdown" lamps.
When test mode is invoked by pressing the push-button on the front panel,
the UPS performs battery impedance testing without interrupting the output
power (even if the battery fails) utilizing a proprietary time-sharing circuit.
The test results are displayed on panel indicators.
End-to-End testing of the UPS is accomplished by cycling the INPUT
ON/OFF switch on the front panel.
The UPS will beep when it operates on battery power or during over-
temperature condition. The alarm may be silenced by pressing the "Alarm
Off" push-button on the front panel.
The
PTC-0
110BA-2 has two double-pole contactors, one on the input and
one on
the output.
The input ON/OFF contactor is controlled by the input ON/OFF switch
located on the front panel.
The Master ON/OFF switch, located on the front panel, shuts down the UPS
and opens both input and output contactors when in the OFF position.
When the two ON/OFF pins are opened the UPS will turn OFF and the
input and output contactors will open. When the two lines are shorted
together the front panel switches determine the status. (The UPS is supplied
with a mating connector and a jumper between the two ON/OFF pins).