PTS 90
123
Series Small Cell
AC Power Distribution Load Centers
Installation Guide
6
All Rights Reserved, 2018
888-820-3508
1.2 Breaker Specifications
Breaker Specifications
PTS P/N
Description
PT-KM1N-07A
UL489A DIN rail Breaker, 07 AMP
PT-KM1N-10A
UL489A DIN rail Breaker, 10 AMP
PT-KM1N-12A
UL489A DIN rail Breaker, 12 AMP
PT-KM1N-16A
UL489A DIN rail Breaker, 16 AMP
Torque Recommendations
Main QOU Breaker
42-47 in-lbs
Load Breaker
17-22 in-lbs
Surge Protection
17-22 in-lbs
Neutral Block and Bar
24-27 in-lbs
Ground Bar
24-27 in-lbs
Caution: Installation shall be completed per all NEC and Local Codes. Do not install
PTS90
123
Systems before reading and understanding all specifications and
installation guides provided. Installation should be performed by a qualified installer.
www.pactechsol.com
www.pactechsol.com
/ATTVendor