background image

EN 

CS10.244 Installation Manual 

 

 

 

Product Description 

The CS10.244 is a DIN-rail mountable single-phase-input power supply, which provides a floating, 
stabilized and galvanically separated SELV/PELV output voltage. 
 

Intended Use 

This device is designed for installation in an enclosure and is intended for commercial use, such as in 
industrial control, process control, monitoring and measurement equipment or the like. Do not use this 
device in equipment where malfunction may cause severe personal injury or threaten human life. 
Without additional measures to reduce the harmonic input current (PFC), the power supply is not 
suited to be connected to the public mains system in residential, commercial and light-industrial 
environments. No additional measures are necessary for use in industrial environments. Exceptions 
for various countries outside the European Union exist and can be determined locally. 
 

Installation Instructions 

Install device in an enclosure providing protection against electrical, mechanical and fire hazards. 
Install the device onto a DIN-rail according to EN 60715 with the input terminals on the bottom of the 
device. Other mounting orientations require a reduction in output current. 
Make sure that the wiring is correct by following all local and national codes. Use appropriate copper 
cables that are designed for a minimum operating temperature of 60°C for ambient temperatures up to 
+45°C, 75°C for ambient temperatures up to +60°C and 90°C for ambient temperatures up to +70°C. 
Ensure that all strands of a stranded wire enter the terminal connection. Unused screw terminals 
should be securely tightened. 
The device is designed for pollution degree 2 areas in controlled environments. No condensation or 
frost allowed. 
The enclosure of the device provides a degree of protection of IP20.

 

The housing does not provide 

protection against spilled liquids. 
The isolation of the device is designed to withstand impulse voltages of overvoltage category III 
according to IEC 60664-1. Above 2000m the overvoltage category is reduced to level II. 
The device is designed as “Class of Protection I” equipment according to IEC 61140. Do not use 
without a proper PE (Protective Earth) connection. 
The device is suitable to be supplied from TN, TT and IT mains networks. The continuous voltage 
between the input terminals and the PE potential must not exceed 300Vac. 
A disconnecting means shall be provided for the input of the device. 
The device is designed for convection cooling and does not require an external fan. Do not obstruct 
airflow and do not cover ventilation grid! 
The device is designed for altitudes up to 6000m (19685ft). See additional requirements in the product 
datasheet for use above 2000m (6560ft). 
Keep the following minimum installation clearances: 40mm on top, 20mm on the bottom, 5mm left and 
right side. Increase the 5mm to 15mm in case the adjacent device is a heat source. When the device 
is permanently loaded with less than 50%, the 5mm can be reduced to zero. 
The device is designed, tested and approved for branch circuits up to 20A without additional protection 
device. If an external fuse is utilized, do not use circuit breakers smaller than 16A B- or 10A C-
Characteristic to avoid a nuisance tripping of the circuit breaker. 
The maximum surrounding air temperature is +70°C (+158°F). The operational temperature is the 
same as the ambient or surrounding air temperature and is defined 2cm below the device. 
The device is designed to operate in areas between 5% and 95% relative humidity. 
 

Installation Instructions for Hazardous Location Areas 

The device is suitable for use in Class I Division 2 Groups A, B, C, D locations. 
Substitution of components may impair suitability for this environment. 
Do not disconnect the device or operate the voltage adjustment unless power has been switched off or 
the area is known to be non-hazardous. 
 

Functional Description 

The output is electronically protected against no-load, overload and short circuit and can supply any 
kind of loads, including inductive and capacitive loads.  
Do not apply return voltages from the load to the output terminals higher than 35V. 
The output voltage can be adjusted with a small flat-blade screwdriver on the front of the unit. 
The green DC-OK LED reports a voltage on the output terminals above 21V. 
The device is equipped with an over-temperature protection. In case of a high temperature, the output 
shuts down and starts automatically again after cooling off. 
Do not parallel devices for higher output currents. 
Same devices can be connected in series for higher output voltages. It is allowed to connect as many 
devices in series as needed, providing the sum of the output voltage does not exceed 150Vdc. 
In case of an internal defect, a redundant circuit limits the maximum output voltage to 39V. The output 
shuts down and automatically attempts to restart. 

 

Technical Data

 

All values are typical figures specified at 230Vac 50Hz input voltage, 24V 
10A output load, 25°C ambient temperature and after a 5 minutes run-in 
time unless otherwise noted. 

Output voltage 

DC 24V 

Nominal 

Adjustment range 

24 – 28Vdc 

Factory setting 24.1V 

Output current 

12.0 – 10.3A 

Below +45°C ambient  

 

10.0 – 8.6A 

At +60°C ambient 

 

7.5 – 6.4A 

At +70°C ambient 

 

Derate linearly b45°C and +70°C 

Input voltage AC 

AC 200-240V 

±10% 

Mains frequency 

50 – 60Hz 

±6% 

Input current AC 

2.2A At 

230Vac 

Power factor 

0.52 At 

230Vac 

Input inrush current 

48A pk 

At 40°C, cold start 

Efficiency 

91.3%  

Power losses 

22.9W  

Hold-up time 

45ms  

Temperature range 

0 to +70°C 

 

Max. wire size (litz wire) 

4mm²  

Wire size AWG 

AWG 20-10 

 

Max. wire diameter 

2.8mm  

Wire stripping length 

7mm / 0.28inch 

 

Tightening torque 

1Nm / 9lb.inch 

 

Size (wxhxd) 

60x124x117mm Without 

DIN-rail 

Weight 

700g / 1.54lb 

 

 
 

Functional Diagram 

+

+

-
-

Output

Overvoltage

Protection

Inrush

Current

Limiter

Output

Voltage

Regulator

Power

Converter

Output

Filter

Output

Power

Manager

Temperature

Shut-down

Input Fuse
Input Filter
Input Rectifier

V

OUT

L

N

DC-OK

LED

 
 

Output Characteristic 

Output voltage

24V

Output current

12V

0V

2A

10A 12A

18A

0A

Adjustment range

28V

4A

14A

A: at -25°C ambient
B: at +25°C ambient
C: at +60°C ambient

6A

8A

16A

A

B

C

 

 
 

Temperature Range 

Allowed output current at 24V

Ambient temperature

0A

0

12A

+45

+70°C

7.5A

10A

+60

A: continuous
B: short term (max. 60s)

A

B

 

 