QS3
Power
Supply
Instruction
Manual
Safety
Separation of output
SELV
IEC/EN 60950-1
EMC
The device is suitable for applications in industrial environment as well as in residential,
commercial and light industry environment without any restrictions.
For further details see datasheet.
PELV
EN 60204-1, EN 50178, IEC 60364-4-41
EMC Immunity
EN 61000-6-1, EN 61000-6-2
Touch current
max. 0.3 mA
Earth leakages current, TN- mains
Isolation resistance
min. 5MOhm
Input to output, 500Vdc
EMC Emission
EN 61000-3-2, EN 61000-3-3, EN 61000-6-3, EN 61000-6-4,
FCC Part 15 Class B
PE resistance
max. 0.1Ohm
Between housing and ground terminal
Transformer
Safety transformer according to IEC/EN 61558-2-17
This device complies with FCC Part 15 rules. Operation is subjected to following two
conditions: (1) this device may not cause harmful interference, and (2) this device must
accept any interference received, including interference that may cause undesired operation.
Approvals
See datasheet or markings on the unit
CE mark in conformance with EMC guideline 89/336/EEC and 93/68/EEC and low-voltage directive (LVD) 73/23/EWG.
Terminals and Connections
Terminals Input
Output
Type
Bi-stable, quick-connect spring clamp terminals
Ferrules
Allowed, but not required
Solid wire
0.5-6mm
2
0.3-4mm
2
Stranded wire
0.5-4mm
2
0.3-2.5mm
2
AWG
AWG 20-10
AWG 28-12
Stripping length
10mm / 0.4inch
6mm / 0.25inch
Pull-out force
10AWG:80N, 12AWG:60N, 14AWG:50N, 16AWG:40N (UL486E)
1. Insert the wire
2. Snap the lever
Use appropriate copper cables that are designed for an operating temperatures of 60°C (for ambient
up to 45°C) and 75°C (for ambient up to 60°C), minimum. Follow national installation codes and
regulations! Ensure that all strands of a stranded wire enter the terminal connection! Up to two
stranded wires with the same cross section are permitted in one connection point (except PE wire). Do
not use without PE (Ground) connection!
Physical Dimensions, Indicators and Cooling
Width
32mm / 1.26’’
Height
124mm / 4.88’’
Depth
102mm / 4.02’’
plus DIN-rail depth
Weight
440g / 0.97lb
DIN-Rail
Use DIN-rails according to EN 60715 or EN 50022
with a height of 7.5 or 15mm
Mounting
Orientation
Output terminal on top and input terminals on the bottom.
For other orientations consult factory.
Indicators
DC-ok LED
(green)
Overload
lamp (red)
Normal operating mode
ON
OFF
BonusPower
®
operation
ON
OFF
Overload (V
OUT
< 90%)
ON
ON
Overload (V
OUT
< 80%)
OFF
ON
Short-circuit (V
OUT
= 0)
OFF
ON
Temperature shut-down
Flashing
Flashing
No input power
OFF
OFF
Do not obstruct air flow!
The unit is convection cooled.
Ventilation grid must be kept free of any obstructions.
Keep installation clearances at higher ambient temperature and full load:
40mm on top, 20mm on the bottom, 5mm on the left and right side are recommended when loaded
permanently with full power. In case the adjacent device is a heat source, 15mm clearance are recommended.
PU-358.010.00-10B
Operation on Two Phases
2
40V
m
a
x.
Fuse
DC
L
N
PE
N
L2
Center
Tap
L1
L3
(1) A phase to phase connection is allowed
as long as the supplying voltage is below
240V
+15%
.
(2) Use a fuse or a circuit breaker to protect
the N input. The N input is internally not
protected and is in this case connected to a
hot wire.
Parallel Operation
Power Supply A
Power Supply B
-
AC
DC
+
-
AC
DC
+
Load
+
-
Fuse
*)
Fuse
*)
(1) Use only power supplies from the same
Dimension Q-series.
(2) Adjust the output voltages of all power
supplies to approximately the same value
(±500mV). Otherwise, the DC-ok signal
might not work properly.
(3) A fuse (or diode) on the output is only
required if more than three units are
connected in parallel.
(4) Keep an installation clearance of 15mm
(left/right) between two power supplies and
avoid installing the power supplies on top of
each other.
Operation with DC Input
Fu
se
+
-
Load
L
N
PE
+
-
Power Supply
AC
DC
Battery
internal
fused
(1) The power supply will operate with a DC
input voltage.
(2) Use a battery or similar DC source.
(3) Cpole to L and –pole to N
(4) In case the –pole of the battery is not
grounded, use an appropriate fuse to protect
the N terminal.
(5) Connect the ground terminal of the power
supply to a PE wire or to machine ground.
Serial Operation
Load
Power Supply A
Power Supply B
+
-
AC
DC
+
-
AC
DC
+
-
Earth
*)
(1) It is possible to connect as many units in
series as needed, providing the sum of the
output voltage does not exceed 150Vdc.
(2) Voltages with a potential above 60Vdc
are not SELV any more and can be
dangerous. Such voltages must be installed
with a protection against touching.
(3) For serial operation use power supplies
of the same type.
(4) Earthing of the output is required when
the sum of the output voltage is above
60Vdc.
(5) Keep an installation clearance of 15mm
(left/right) between two power supplies and
avoid installing the power supplies on top of
each other.
Check touch current
(earth leakage current)! The total touch current is the sum
of the touch currents of all units. Safety limits – depending on the field of
application - apply for the allowed touch current!
Air flow
open
close