FPS300.241-002-101 Installation Manual 

 

 

 

 

Product Description

 

The FPS300.241-002-101 is a stand-alone power supply for single phase mains systems, which 
provides a stabilized and galvanically separated PELV/ES1 output voltage. The negative potential of 
the outputs is permanently connected to PE within the unit.

 

The housing is rated as IP65 and IP67 according IEC60529 and provides protection against electrical, 
mechanical and fire hazards.

 

Intended Use

 

This indoor use device is intended for commercial use, such as in industrial control, process control, 
monitoring, measurement or the like.

 

Do not use this device in equipment, where malfunctioning may cause severe personal injury or 
threaten human life, without additional appropriate safety devices, that are suited for the end-
application.

 

If used in a manner outside of its specification, the protection provided by the device may be impaired.

 

Installation Instructions

 

Install the device with the terminals on the bottom of the device. Other mounting orientations require a 
reduction in output current.

 

When installing watch out for the risk of injury from sharp edges and assure that when installed any 
sharp edges on the back cannot be accessed and cannot cause injury.

 

Use 4 screws ( 2 on top and 2 on bottom mounting holes) suitable for the underground and a strength 
comparable to M4 or UNC 8-32 screws.

 

The device is designed for pollution degree 3 areas in controlled environments.

 

The enclosure of the device provides a degree of ingress protection of IP65 and IP67 when installed 
with all mating connectors firmly connected. Assure that during installation no moisture or dirt gets into 
the connections. Operation in wet locations or in areas where moisture or condensation can be 
expected is possible.

 

The isolation of the device is designed to withstand impulse voltages of overvoltage category III 
according to IEC 60664-1.

 

The device is designed as "Class of Protection I" equipment according to IEC 61140. Do not use 
without a proper PE (Protective Earth) connection.

 

The device is suitable to be supplied from TN, TT or IT mains networks. The voltage between the input 
terminals and the PE potential must not exceed 264Vac. 

 

The device is designed for convection cooling without a fan. Do not obstruct airflow.

 

The device is designed for altitudes up to 5000m (16400ft). Above 2000m (6560ft) a reduction in 
output current and overvoltage category is required.

 

Keep the following minimum installation clearances: 30mm on top and bottom, 10mm on the front, the 
left and the right side.

 

The device is designed, tested and approved for branch circuits up to 20A (UL) and 32A (IEC) without 
additional protection device. If an external fuse is utilized, do not use circuit breakers smaller than 6A 
B- or C-characteristic to avoid a nuisance tripping of the circuit breaker. For DC supply voltages above 
150Vdc an external circuit breaker (rated 6A with B- or C-characteristic) is required. 
Make sure that you only use plugs and cables rated for the device output current and the required 
temperature range. Follow all local and national codes for installation.

 

Do not connect devices in parallel for higher output currents.

 

The maximum permissible ambient air temperature is +70°C (+158°F). The operational temperature is 
the same as the ambient or ambient air temperature and is defined 2cm below the device.

 

Cleaning only with a damp cloth.

 

Functional Description

 

The output is electronically protected against no-load, overload and short circuit and can supply any 
kind of loads, including inductive and capacitive loads. If capacitors with a capacitance >100mF are 
connected, the unit might charge the capacitor in an intermittent mode.

 

Do not apply return voltages from the load to the output terminals higher than 35V.

 

The green Status LED reports an output above 90% of the adjusted voltage of a running device.

 

The DC-OK contact is closed when the Status LED is green.

 

Contact ratings: 60Vdc 0.3A, 30Vdc 1A, 30Vac 0.5A for resistive loads.

 

The device has an internal overtemperature protection. If the temperature is too high the output shuts 
down and starts automatically again after cooling off.

 

In case of an internal defect, a redundant circuit limits the maximum output voltage to 32.5V. The 
output shuts down and automatically attempts to restart.

 

LED bargraph and push-buttons:

 

The LED bar normally displays the actual output power as percentage value. 100% equals an output 
power of 300W. LEDs up to and including 100% are green, the LEDs above 100% are orange.  
If you press the "Set Mode" button for 3 seconds all LEDs light up briefly and one LED stays on, 
showing the actual output voltage. With pressing the up or down button you can change the set 
voltage to the predefined values: 24V, 24.5V, 25V, 25.5V, 26V, 26.5V, 27V and 28V as printed aside 
the LEDS. The voltage is set immediately and the value stored until the next change. If no button is 
pressed for 15s unit returns to the normal state the LED bar will return to show the output power.

 

Mating connectors:

 

Use a Harting HANQ4/2 female plug to connect to the input voltage connector (X1). Pin assignment: 
Pin 1 for L; Pin 4 for N; Pin PE for PE.

 

Use a standard M12 A-coded 5 pin female plug to connect to the DC OK signal connector (X2).

 

Pin assignment: Pin 1 and Pin 4 for relay contact.

 

Use a Harting HANQ4/0 male plug to connect to the output voltage connector (X3). Pin assignment: 
Pin 3 for plus; Pin 2 for minus; Pin 1 and 4 are not connected. 
 
 
 
 
 
 
 
 
 

 

Technical Data

 

All values are typical figures specified at 100V/230Vac 50Hz input voltage, 
24V, 300W output load, 25°C ambient temperature and after a 5 minutes 
run-in time unless otherwise noted. 

Output voltage 

DC 24V 

Nominal 

Adjustment range 

24 

 28Vdc 

Factory setting 24.5V 

Output power 

 

Continuous:

 

360W 

Below +45°C ambient 

 

300W 

At +55°C ambient 

 

150W 

At +70°C ambient 

Short-term, up to 5s:

 

600W 

Below +55°C ambient: 
Vin >=100VAC 

 

300W 

At +70°C ambient 

 

Derate linearly above +45°C and max. 70°C 

Input voltage AC 

AC 100 - 240V 

-15% / +10% 

Mains frequency 

50 

 60Hz 

±6% 

Input current AC 

4.0 / 1.7A 

At 100 / 230 Vac 

Power factor 

0.99 / 0.97 

At 120 / 230 Vac 

Input voltage DC 

DC 110-300V*) 

±20% 

Input current DC 

3.6A / 1.3A 

At 110 / 300Vdc 

Input inrush current 

2.6 / 6A peak 

at 25°C 120 /230 Vac 

Efficiency 

93.4 / 95% 

At 100 / 230 Vac 

Hold-up time 

33 / 33ms 

At 100 / 230Vac 

Temperature range 

-25 to +70°C 

 

Size 

(LxWxH)

 

183x182x59mm 

Without connectors 

Weight 

1200g / 2.7lb 

 

*) For DC supply voltages above 150Vdc an external circuit 
breaker is required (rated 6A with B- or C-characteristic).

 

Functional Diagram 

 

 

Output Characteristic 

 

 

Temperature Range 

 

 

Hole Pattern for Mounting 

 

All dimensions in mm; connectors X1 to X3 from left to right 

 