background image

PIM60.241

Feb. 2022 / Rev. 2.0 DS-PIM60.241-EN

www.pulspower.com

1 / 17

All parameters are specified at 24V, 2.5A, 230Vac, 25°C ambient and after a 5 minutes run-in time unless otherwise noted.

P

OWER SUPPLY

1AC 24V 60W

AC 100-240V Wide-range input

NEC CLASS 2 compliant

Cost optimized without compromising quality or
reliability

No PE connection required

Width only 36mm

Efficiency up to 91.8%

Low no-load power losses

Full power between -10°C and +60°C

Push-in terminals

3 Year warranty

P

RODUCT DESCRIPTION

S

HORT-FORM DATA

The  PIM60.241  is  a  DIN  rail  mountable  single-phase-
input  power  supply,  which  provides  a  floating,
stabilized  and  galvanically  separated  SELV/PELV/ES1
output  voltage.  The  output  fulfils  the  requirements
for a limited power source according to NEC CLASS 2.

The device is equipped with Push-in terminals, which
are optimized for automated wiring.

The  mechanically  robust  housing  is  made  of  a  high-
grade,  reinforced  molded  material,  which  permits
surrounding temperatures up to +70°C.

The unit is designed as “Class of Protection” II unit and
fulfills  the  safety  and  EMC  requirements  without  an
input PE connection. This saves wiring costs.

The PIANO family is a compact industrial grade DIN rail
power  supply  series  that  focuses  on  the  essential
features needed in today’s industrial applications. The
excellent cost/performance ratio does not compromise
quality or reliability.

Output voltage

DC 24V

Nominal

Adjustment range 24-28V

Factory setting 24.1V

Output current

2.5-2.1A

Below +60°C ambient

1.9-1.6A

At +70°C ambient

Derate b60°C and +70°C

Input voltage AC

AC 100-240V

±

 10%

Mains frequency

50-60Hz

±

6%

Input current AC

1 / 0.6A

At 120 / 230Vac

Power factor

0.55 / 0.47

At 120 / 230Vac

Input inrush

current

15 / 36A

peak

At 120 / 230Vac, +40°C,

cold start

Efficiency

90.7 / 91.8%

At 120 / 230Vac

Power losses

6.2 / 5.4W

At 120 / 230Vac

Hold-up time

24 / 113ms

At 120 / 230Vac

Temperature

range

-10°C to +70°C

Size (w x h x d)

36x90x91mm

Without DIN rail

Weight

225g / 0.5lb

O

RDER NUMBERS

M

AIN APPROVALS

Description:

Power supply PIM60.241-xx

Order Number:
PIM60.241

For details and the complete approval list, see chapter 18.

Ind. Cont. Eq.

Summary of Contents for PIANO PIM60.241

Page 1: ...rounding temperatures up to 70 C The unit is designed as Class of Protection II unit and fulfills the safety and EMC requirements without an input PE connection This saves wiring costs The PIANO famil...

Page 2: ...ntly changing the information in this data sheet is subject to revision We therefore kindly ask you to always use the latest issue of this document available under www pulspower com No part of this do...

Page 3: ...ith the input terminals on the bottom of the device Make sure that the wiring is correct by following all local and national codes Use appropriate copper cables that are designed for a minimum operati...

Page 4: ...Fig 3 1 Shut down voltage typ 54Vac Steady state value see Fig 3 1 External input protection See recommendations in chapter 2 AC 100V AC 120V AC 230V Input current typ 1 15A 1A 0 6A At 24V 2 5A see Fi...

Page 5: ...mpact on the inrush current value The charging current into EMI suppression capacitors is disregarded in the first microseconds after switch on AC 100V AC 120V AC 230V typ 12A 15A 36A At 40 C ambient...

Page 6: ...value which can be achieved Factory settings typ 24 1V 0 2 at full load cold unit Line regulation max 10mV Between 90 and 300Vac Load regulation max 100mV Between 0 and 2 5A static value see Fig 6 1...

Page 7: ...oltage remains within specification following the loss of input power The hold up time is output load dependent At no load the hold up time can be up to several seconds The green DC OK LED is also on...

Page 8: ...W 0 3W 0 4W At no load typ 3 8W 3 5W 3 4W At 24V 1 25A half load typ 7 1W 6 2W 5 4W At 24V 2 5A full load The average efficiency is an assumption for a typical application where the device is loaded w...

Page 9: ...V 1 25A and 25 C 10 MTBF MTBF stands for Mean Time Between Failure which is calculated according to statistical device failures and indicates reliability of a device It is the statistical representati...

Page 10: ...11 1 Functional diagram 12 Terminals And Wiring The terminals are IP20 Finger safe constructed and suitable for field and factory wiring All Terminals Type Push in terminals Solid wire max 2 5mm2 Stra...

Page 11: ...se noted 13 Front Side And User Elements A Input Terminals N Neutral conductor input L Phase Line input B OutputTerminals Dual terminals for the negative and positive pole Both poles are internally co...

Page 12: ...iterion A Conducted disturbance EN 61000 4 6 0 15 80MHz 10V Criterion A Voltage dips EN 61000 4 11 0 of 100Vac 0Vac 20ms Criterion A C 40 of 100Vac 40Vac 200ms Criterion C 70 of 100Vac 70Vac 500ms Cri...

Page 13: ...the derated current limits in order not to overload the unit Humidity 5 to 95 r h According to IEC 60068 2 30 No condensation allowed Atmospheric pressure 110 54kPa See Fig 15 2 for details Altitude...

Page 14: ...ins IT mains typ 100 A 200 A At 230Vac 50Hz TN TT mains IT mains max 60 A 100 A At 110Vac 50Hz TN TT mains IT mains max 80 A 150 A At 132Vac 60Hz TN TT mains IT mains Touch current leakage current max...

Page 15: ...ts for supply voltages up to 1100V Particular requirements and tests for switch mode power supply units and transformers for switch mode power supply units ISA 71 04 1985 Manufacturer s Declaration On...

Page 16: ...eight Width 36mm 1 42 Height 90mm 3 54 Depth 91mm 3 58 The DIN rail height must be added to the unit depth to calculate the total required installation depth Weight 225g 0 5lb DIN rail Use 35mm DIN ra...

Page 17: ...NDANCY Do not use this device to build redundant systems since there is no monitoring DC OK signal included 21 5 TWO PHASE OPERATION The power supply can also be operated on two phases of a three phas...

Reviews: