PIM60.241

Feb. 2022 / Rev. 2.0 DS-PIM60.241-EN

www.pulspower.com

12 / 17

All parameters are specified at 24V, 2.5A, 230Vac, 25°C ambient and after a 5 minutes run-in time unless otherwise noted.

14. EMC

The EMC behavior of the device is designed for applications in industrial environment as well as in residential, commercial
and light industry environments.

The device complies with EN 61000-6-1, EN 61000-6-2, EN 61000-6-3, EN 61000-6-4, EN 61000-3-2 and EN 61000-3-3. The
device complies with FCC Part 15 rules. Operation is subjected to following two conditions: (1) this device may not cause
harmful  interference,  and  (2)  this  device  must  accept  any  interference  received,  including  interference  that  may  cause
undesired operation.

Do not use this device on AC 100V mains with more than 1.9A load when the application is sensitive to short output voltage
dips during mains interruptions even with a length shorter than 20ms.

EMC Immunity

Electrostatic discharge

EN 61000-4-2

Contact discharge

8kV

Criterion A

Air discharge

8kV

Criterion A

Electromagnetic RF field

EN 61000-4-3

80MHz - 6GHz

10V/m

Criterion A

Fast transients (Burst)

EN 61000-4-4

Input lines

4kV

Criterion A

Output lines

2kV

Criterion A

Surge voltage on input

EN 61000-4-5

 N

2kV

Criterion A

N / L 

 Earthed output

4kV

Criterion A

Surge voltage on output

EN 61000-4-5

(+) 

 (−)

1kV

Criterion A

(+) 

 (−) Earthed

1kV

Criterion A

(−) 

 (+) Earthed

1kV

Criterion A

Conducted disturbance

EN 61000-4-6

0.15 - 80MHz

10V

Criterion A

Voltage dips

EN 61000-4-11

0% of 100Vac

0Vac, 20ms

Criterion A/C

40% of 100Vac

40Vac, 200ms

Criterion C

70% of 100Vac

70Vac, 500ms

Criterion A

0% of 120Vac

0Vac, 20ms

Criterion A

40% of 120Vac

48Vac, 200ms

Criterion C

70% of 120Vac

84Vac, 500ms

Criterion A

0% of 200Vac

0Vac, 20ms

Criterion A

40% of 200Vac

80Vac, 200ms

Criterion A

70% of 200Vac

140Vac, 500ms

Criterion A

Voltage interruptions

EN 61000-4-11

0V

5000ms

Criterion C

Powerful transients

VDE 0160

Over entire load range

750V, 1.3ms

Criterion A

Performance criterions:
A:

The device shows normal operation behavior within the defined limits.

B:

The device operates continuously during and after the test. During the test minor temporary impairments may
occur, which will be corrected by the device itself.

C:

Temporary loss of function is possible. The device may shut-down and restarts by itself. No damage or hazards
for the device will occur.

A/C: Criterion A for output current below 1.9A and criterion C for output currents above 1.9A.

EMC Emission
Conducted emission input lines

EN 55011, EN 55032, FCC Part 15, CISPR 11,

CISPR32

Class B

Conducted emission output lines

IEC/CISPR 16-1-2, IEC/CISPR 16-2-1

Limits for local DC power networks

fulfilled.

Radiated emission

EN 55011, EN 55032, CISPR 11, CISPR 32

Class B

Harmonic input current

EN 61000-3-2

Fulfilled (Class A)

Voltage fluctuations, flicker

EN 61000-3-3

Fulfilled, tested with non pulsing

constant current loads.

Switching Frequencies

Main converter

2kHz to 130kHz

Input voltage and output load
dependent

Summary of Contents for PIANO PIM60.241

Page 1: ...rounding temperatures up to 70 C The unit is designed as Class of Protection II unit and fulfills the safety and EMC requirements without an input PE connection This saves wiring costs The PIANO famil...

Page 2: ...ntly changing the information in this data sheet is subject to revision We therefore kindly ask you to always use the latest issue of this document available under www pulspower com No part of this do...

Page 3: ...ith the input terminals on the bottom of the device Make sure that the wiring is correct by following all local and national codes Use appropriate copper cables that are designed for a minimum operati...

Page 4: ...Fig 3 1 Shut down voltage typ 54Vac Steady state value see Fig 3 1 External input protection See recommendations in chapter 2 AC 100V AC 120V AC 230V Input current typ 1 15A 1A 0 6A At 24V 2 5A see Fi...

Page 5: ...mpact on the inrush current value The charging current into EMI suppression capacitors is disregarded in the first microseconds after switch on AC 100V AC 120V AC 230V typ 12A 15A 36A At 40 C ambient...

Page 6: ...value which can be achieved Factory settings typ 24 1V 0 2 at full load cold unit Line regulation max 10mV Between 90 and 300Vac Load regulation max 100mV Between 0 and 2 5A static value see Fig 6 1...

Page 7: ...oltage remains within specification following the loss of input power The hold up time is output load dependent At no load the hold up time can be up to several seconds The green DC OK LED is also on...

Page 8: ...W 0 3W 0 4W At no load typ 3 8W 3 5W 3 4W At 24V 1 25A half load typ 7 1W 6 2W 5 4W At 24V 2 5A full load The average efficiency is an assumption for a typical application where the device is loaded w...

Page 9: ...V 1 25A and 25 C 10 MTBF MTBF stands for Mean Time Between Failure which is calculated according to statistical device failures and indicates reliability of a device It is the statistical representati...

Page 10: ...11 1 Functional diagram 12 Terminals And Wiring The terminals are IP20 Finger safe constructed and suitable for field and factory wiring All Terminals Type Push in terminals Solid wire max 2 5mm2 Stra...

Page 11: ...se noted 13 Front Side And User Elements A Input Terminals N Neutral conductor input L Phase Line input B OutputTerminals Dual terminals for the negative and positive pole Both poles are internally co...

Page 12: ...iterion A Conducted disturbance EN 61000 4 6 0 15 80MHz 10V Criterion A Voltage dips EN 61000 4 11 0 of 100Vac 0Vac 20ms Criterion A C 40 of 100Vac 40Vac 200ms Criterion C 70 of 100Vac 70Vac 500ms Cri...

Page 13: ...the derated current limits in order not to overload the unit Humidity 5 to 95 r h According to IEC 60068 2 30 No condensation allowed Atmospheric pressure 110 54kPa See Fig 15 2 for details Altitude...

Page 14: ...ins IT mains typ 100 A 200 A At 230Vac 50Hz TN TT mains IT mains max 60 A 100 A At 110Vac 50Hz TN TT mains IT mains max 80 A 150 A At 132Vac 60Hz TN TT mains IT mains Touch current leakage current max...

Page 15: ...ts for supply voltages up to 1100V Particular requirements and tests for switch mode power supply units and transformers for switch mode power supply units ISA 71 04 1985 Manufacturer s Declaration On...

Page 16: ...eight Width 36mm 1 42 Height 90mm 3 54 Depth 91mm 3 58 The DIN rail height must be added to the unit depth to calculate the total required installation depth Weight 225g 0 5lb DIN rail Use 35mm DIN ra...

Page 17: ...NDANCY Do not use this device to build redundant systems since there is no monitoring DC OK signal included 21 5 TWO PHASE OPERATION The power supply can also be operated on two phases of a three phas...