All parameters are specified at 24V, 2.5A, 230Vac, 25°C ambient and after a 5 minutes run-in time unless otherwise noted.

15. Environment

Operational temperature

-10°C to +70°C (14°F to 158°F)

The operational temperature is the ambient or
surrounding temperature and is defined as the
air temperature 2cm below the device.

Storage temperature

-40°C to +85°C (-40°F to 185°F)

For storage and transportation

Output derating

0.06A/°C

B60°C and +70°C (140°F to 158°F)

0.15A/1000m or 5°C/1000m

For altitudes >2000m (6560ft), see Fig. 15-2

The derating is not hardware controlled. The user has to take this into consideration to
stay below the derated current limits in order not to overload the unit.

Humidity

5 to 95% r.h.

According to IEC 60068-2-30
No condensation allowed.

Atmospheric pressure

110-54kPa

See Fig. 15-2 for details

Altitude

Up to 5000m (16 400ft)

See Fig. 15-2 for details

Over-voltage category

II

According to IEC 60664-1, for altitudes
<5000m

Impulse withstand voltage

4kV (according to over-voltage
category III)

Input to PE
According to IEC 60664-1, for altitudes
<2000m

Degree of pollution

2

According to IEC 60664-1, non conductive

Vibration sinusoidal

2-17.8Hz: ±1.6mm
17.8-500Hz: 2g
2 hours / axis

According to IEC 60068-2-6

Shock

30g 6ms, 20g 11ms
3 bumps / direction, 18 bumps in total

According to IEC 60068-2-27

Shock and vibration is tested in combination with DIN rails according to EN 60715 with
a height of 15mm and a thickness of 1.3mm.

Fig. 15-1: Output power vs. ambient temp.

Fig. 15-2: Output power vs. altitude

Summary of Contents for PIANO PIM60.241

Page 1: ...rounding temperatures up to 70 C The unit is designed as Class of Protection II unit and fulfills the safety and EMC requirements without an input PE connection This saves wiring costs The PIANO famil...

Page 2: ...ntly changing the information in this data sheet is subject to revision We therefore kindly ask you to always use the latest issue of this document available under www pulspower com No part of this do...

Page 3: ...ith the input terminals on the bottom of the device Make sure that the wiring is correct by following all local and national codes Use appropriate copper cables that are designed for a minimum operati...

Page 4: ...Fig 3 1 Shut down voltage typ 54Vac Steady state value see Fig 3 1 External input protection See recommendations in chapter 2 AC 100V AC 120V AC 230V Input current typ 1 15A 1A 0 6A At 24V 2 5A see Fi...

Page 5: ...mpact on the inrush current value The charging current into EMI suppression capacitors is disregarded in the first microseconds after switch on AC 100V AC 120V AC 230V typ 12A 15A 36A At 40 C ambient...

Page 6: ...value which can be achieved Factory settings typ 24 1V 0 2 at full load cold unit Line regulation max 10mV Between 90 and 300Vac Load regulation max 100mV Between 0 and 2 5A static value see Fig 6 1...

Page 7: ...oltage remains within specification following the loss of input power The hold up time is output load dependent At no load the hold up time can be up to several seconds The green DC OK LED is also on...

Page 8: ...W 0 3W 0 4W At no load typ 3 8W 3 5W 3 4W At 24V 1 25A half load typ 7 1W 6 2W 5 4W At 24V 2 5A full load The average efficiency is an assumption for a typical application where the device is loaded w...

Page 9: ...V 1 25A and 25 C 10 MTBF MTBF stands for Mean Time Between Failure which is calculated according to statistical device failures and indicates reliability of a device It is the statistical representati...

Page 10: ...11 1 Functional diagram 12 Terminals And Wiring The terminals are IP20 Finger safe constructed and suitable for field and factory wiring All Terminals Type Push in terminals Solid wire max 2 5mm2 Stra...

Page 11: ...se noted 13 Front Side And User Elements A Input Terminals N Neutral conductor input L Phase Line input B OutputTerminals Dual terminals for the negative and positive pole Both poles are internally co...

Page 12: ...iterion A Conducted disturbance EN 61000 4 6 0 15 80MHz 10V Criterion A Voltage dips EN 61000 4 11 0 of 100Vac 0Vac 20ms Criterion A C 40 of 100Vac 40Vac 200ms Criterion C 70 of 100Vac 70Vac 500ms Cri...

Page 13: ...the derated current limits in order not to overload the unit Humidity 5 to 95 r h According to IEC 60068 2 30 No condensation allowed Atmospheric pressure 110 54kPa See Fig 15 2 for details Altitude...

Page 14: ...ins IT mains typ 100 A 200 A At 230Vac 50Hz TN TT mains IT mains max 60 A 100 A At 110Vac 50Hz TN TT mains IT mains max 80 A 150 A At 132Vac 60Hz TN TT mains IT mains Touch current leakage current max...

Page 15: ...ts for supply voltages up to 1100V Particular requirements and tests for switch mode power supply units and transformers for switch mode power supply units ISA 71 04 1985 Manufacturer s Declaration On...

Page 16: ...eight Width 36mm 1 42 Height 90mm 3 54 Depth 91mm 3 58 The DIN rail height must be added to the unit depth to calculate the total required installation depth Weight 225g 0 5lb DIN rail Use 35mm DIN ra...

Page 17: ...NDANCY Do not use this device to build redundant systems since there is no monitoring DC OK signal included 21 5 TWO PHASE OPERATION The power supply can also be operated on two phases of a three phas...

Reviews: