PIM60.241
Feb. 2022 / Rev. 2.0 DS-PIM60.241-EN
www.pulspower.com
7 / 17
All parameters are specified at 24V, 2.5A, 230Vac, 25°C ambient and after a 5 minutes run-in time unless otherwise noted.
7.
Hold-up Time
The hold-up time is the time during which a device’s output voltage remains within specification following the loss of input
power. The hold-up time is output load dependent. At no load, the hold-up time can be up to several seconds. The green
DC-OK LED is also on during this time.
AC 100V
AC 120V
AC 230V
Hold-up time
typ.
14ms
24ms
113ms
At 24V, 2.5A
typ.
38ms
58ms
230ms
At 24V, 1.25A
min.
11ms
19ms
90ms
At 24V, 2.5A
min.
30ms
46ms
184ms
At 24V, 1.25A
Fig. 7-1: Hold-up time vs. input voltage
Fig. 7-2: Shut-down behaviour, definitions