SLA3.100 Installation Manual 

 

 

 

Product Description 

The SLA3.100

 

is a DIN-rail mountable single-phase-input power supply, which provides network 

power for the AS-Interface

®

 system. The AS-Interface

®

 system is a field bus technology, where power 

and data are provided by the same single two-conductor wire. Therefore, special power supplies with 
an integrated data-decoupling circuit are required to prevent the modulated signal voltage on the AS-
Interface

®

 bus from being corrupted. 

The output of the device fulfils the requirements for a limited power source according to NEC Class 2. 
 

Intended Use

 

This device is designed for installation in an enclosure and is intended for commercial use to supply 
power to AS-Interface

®

 network systems. 

Do not use this device in equipment, where malfunctioning may cause severe personal injury or 
threaten human life without additional appropriate safety devices, that are suited for the end-
application. 
If this device is used in a manner outside of its specification, the protection provided by the device may 
be impaired. 
When operating without AS-Interface structure (e.g. in a laboratory test), connect a 470

μ

F/35V 

capacitor between AS-Int and AS-Interface – terminals to avoid output voltage oscillations. 
 

Installation Instructions 

Install device in an enclosure providing protection against electrical, mechanical and fire hazards. 
Install the device onto a DIN-rail according to EN 60715 with the input terminals on the bottom of the 
device. 
Make sure that the wiring is correct by following all local and national codes. Use appropriate copper 
cables that are designed for a minimum operating temperature of 60°C for ambient temperatures up to 
+45°C, 75°C for ambient temperatures up to +60°C and 90°C for ambient temperatures up to +70°C. 
Ensure that all strands of a stranded wire enter the terminal connection. Unused screw terminals 
should be securely tightened. 
The device is designed for pollution degree 2 areas in controlled environments. No condensation or 
frost is allowed. 
The enclosure of the device provides a degree of protection of IP20. The housing does not provide 
protection against spilled liquids. 
The device is designed for overvoltage category II zones. 
The device is designed as “Class of Protection I” equipment according to IEC 61140. Do not use 
without a proper PE (Protective Earth) connection. 
The device is suitable to be supplied from TN, TT and IT mains networks. The continuous voltage 
between the input terminals and the PE potential must not exceed 300Vac. 
A disconnecting means shall be provided for the input of the device. 
The device is designed for convection cooling and does not require an external fan. Do not obstruct 
airflow and do not cover ventilation grid! 
The device is designed for altitudes up to 2000m (6560ft). 
Keep the following minimum installation clearances: 40mm on top, 20mm on the bottom, 5mm left and 
right side. Increase the 5mm to 15mm in case the adjacent device is a heat source. When the device 
is permanently loaded with less than 50%, the 5mm can be reduced to zero. 
The device is designed, tested and approved for branch circuits up to 20A without additional protection 
device. If an external fuse is utilized, do not use circuit breakers smaller than 10A B- or 6A C-
Characteristic to avoid a nuisance tripping of the circuit breaker. 
The maximum surrounding air temperature is +70°C (+158°F). The operational temperature is the 
same as the ambient or surrounding air temperature and is defined 2cm below the device. 
The device is designed to operate in areas between 10% and 90% relative humidity. 
 

Installation Instructions for Hazardous Location Areas 

The device is suitable for use in Class I Division 2 Groups A, B, C, D locations and for use in Group II 
Category 3 (Zone 2) environments. 
Hazardous Location Classification: ATEX: EPS 13 ATEX 1 555 X, II 3G EX nA IIC T3 Gc 

WARNING EXPLOSION HAZARDS! 

Substitution of components may impair suitability for this environment. 
Do not disconnect the device or operate the voltage adjustment unless power has been switched off or 
the area is known to be non-hazardous. 
A suitable enclosure must be provided for the end product which has a minimum protection of IP54 
and fulfils the requirements of the EN 60079-0. 
 

Functional Description 

The output is electronically protected against no-load, overload and short circuit. 
The green AS-i-OK LED reports a nominal output voltage of a running device. The LED is off as soon 
as the unit is in overload mode. 
Do not parallel devices for higher output currents. 
Do not connect outputs of devices in a series connection for higher output voltages. 
In case of an internal defect, a redundant circuit limits the maximum output voltage to 55V. The output 
shuts down and automatically attempts to restart. 
The device is equipped with a manual input range selector. When used on 100-120V mains, set the 
switch into the 115V position. 
The device is equipped with an "IR addressing mode" feature, which is selectable via jumper on the 
front of the unit. The addressing mode interrupts the data communication on the yellow AS-Interface 
cable. Participants with an infrared interface can then quickly be assigned a new ID address by means 
of an infrared programming unit without the need to disconnect them from the AS-Interface cable. 
Afterwards, the "Communication Mode" can be selected again to restart the data communication. The 
red LED reports an active IR-mode and a disabled communication on the yellow AS-Interface cable. 

 

Technical Data

 

All values are typical figures specified at 230Vac 50Hz input voltage, 30.6V 
2.8A output load, 25°C ambient temperature and after a 5 minutes run-in 
time unless otherwise noted. 

Output voltage 

DC 30.6V 

Nominal 

Adjustment range 

Not adjustable 

Factory setting 30.6V 

Output current 

2.8A 

Below +60°C ambient  

 

2.1A At 

+70°C 

ambient 

 

Derate linearly b60°C and +70°C 

 

For use on AS-Interface

®

 networks only 

Current limitation 

>3.2A  

Input voltage AC 

AC 100-120V / 
220-240V 

-15% / +10% 
manual select 

Mains frequency 

50 – 60Hz 

±6% 

Input current AC 

1.4 / 0.77A 

At 120 / 230Vac 

Power factor 

0.58 / 0.53 

At 120 / 230Vac 

Input inrush current 

18 / 32A pk 

At 120 / 230Vac, 40°C, 
cold start 

Efficiency 

89.5 / 90.5% 

At 120 / 230Vac 

Power losses 

10.0 / 9.1W 

At 120 / 230Vac 

Hold-up time 

55 / 58ms 

At 120 / 230Vac 

Temperature range 

-10 to +70°C 

 

Max. wire size (litz wire) 

4mm² Power 

terminals 

Wire size AWG 

AWG 20-10 

Power terminals 

Max. wire diameter 

2.8mm Power 

terminals 

Wire stripping length 

7mm / 0.28inch 

Power terminals 

Tightening torque 

1Nm / 9lb.inch 

Power terminals 

Size 

(wxhxd)

 

49x124x102mm Without 

DIN-rail 

Weight 

500g / 1.1lb 

 

 
 

Functional Diagram 

Input

Fuse

&

Input

Filter

L

N

Output

Overvoltage

Protection

Input

Rectifier

&

Inrush

Limiter

AS-i +

Output

Filter

AS-i-ok

(green)

Power

Converter

Shield

115/230V

Manual

Switch

230

Communication/

IR Mode

AS-i

Decoupling

Unit

IR Mode

(red)

AS-i +

AS-i -

AS-i -

 
 

Output Characteristic 

Output voltage

Output current

15V

0V

1A

2A

3A

0A

30.6V

4A

 
 

Temperature Range 

Allowed output current

Ambient temperature

0A

-10

2.8A

+60

+70°C

2.1A

A: continuous

B: short term (max. 60s)

A

B

 