UBC10 Instruction Manual  

UBC10 Bedienungsanleitung 

 

 

   

 

User Interface 

A Power 

Port 

 

 

Quick-connect spring-clamp terminals, for input voltage and output 

voltage.  

B Signal Port 

 

Plug connector, inserted from the bottom. Connections for the 

Ready, Buffering, Replace Battery relay contacts and for the Inhibit 
input. 

C Green Status LED   (see Fig. 1 for LED pattern) 

 Ready: 

Battery is charged, no wiring failure is recognized, input 

voltage is sufficient and inhibit signal is not active. 

 Charging: Battery is charging and the battery capacity is below 

85%. 

 Buffering: Unit is in buffer mode. 

D  Yellow Diagnosis LED   (see Fig. 2 for LED pattern) 

 Overload: 

Output has switched off due to long overload in buffer 

mode or due to high temperature. 

 Replace 

battery: 

Indicates a battery which failed the battery quality 

test (SoH test). Battery should be replaced soon. 

 Buffer-time 

expired: 

Output has switched off due to setting of 

Buffer-timer Limiter. This signal will be displayed for 15 minutes. 

 Inhibit 

active: 

Indicates that buffering is disabled due to an active 

inhibit signal. 

E  Red Check Wiring LED 

 

This LED indicates a failure in the wiring, battery, battery fuse or 
installation (e.g. too low input voltage). 

F Buffer-time 

Limiter 

 

This dial limits the maximum buffer time during a buffer event to 
save the battery energy, for a faster recharge and to expand the 
battery life. 

 

Benutzer Schnittstelle 

A Leistungsanschlüsse  

 

Federkraftklemmen für die Eingangs- und Ausgangsspannung. 

B Signalanschlüsse  

 

Steckverbinder von unten einsteckbar. Anschlüsse für die Ready, 
Buffering, Replace Battery Relaiskontakte und für den Inhibit Eingang.
 

C  Grüne „Status“ LED     (Blinkmuster ist in Bild 1 erklärt) 

Ready: Die DC-USV ist pufferbereit. Batterie ist geladen, kein Inhibit 
Signal, kein Verdrahtungsfehler, Eingangsspannung ist ausreichend. 

Charging: Die Batterie wird geladen und hat einen Ladezustand von 
weniger als 85%.  

Buffering: Die DC-USV ist im Pufferbetrieb. 

D  Gelbe „Diagnosis“ LED   (Blinkmuster ist in Bild 2 erklärt) 

Overload: Meldet einen abgeschalteten Ausgang, aufgrund von 
Überlast während des Pufferbetriebes oder Übertemperatur. 

Replace battery: Meldet, wenn die Batterie den Qualitätstest nicht 
besteht. Batterie sollte baldmöglichst ersetzt werden. 

Buffer-time expired: Meldet einen abgeschalteten Ausgang, 
aufgrund von abgelaufener Pufferzeit (Buffer-Time-Limiter). Die 
Meldung wird gespeichert und 15 Minuten lang angezeigt. 

Inhibit active: Ein aktives Inhibit Signal verhindert eine Pufferung. 

Rote „Check Wiring“ LED 

Meldet eine notwendige Überprüfung der Verdrahtung zwischen DC-
USV und Batterie sowie eine notwendige Überprüfung der Batterie 
selbst. Meldet auch, wenn die Eingangsspannung zu klein ist. 

F “Buffer-time 

Limiter” 

 

Mit diesem Einstellregler lässt sich die Pufferzeit begrenzen um die 
Batterie zu schonen, und eine schnellere Nachladung zu erreichen. 

Ready (1-2) 

Buffering (2-3)  

Replace Battery (5-6) 

Inhibit (7-8) 

Contact is closed when battery is charged and unit is ready to buffer. 
Contact is closed when unit is buffering. 
Contact is closed when a replacement of the battery is necessary. 
Buffering is disabled when an voltage > 10V is applied to the pins. 
Relay contact rating: max. 60Vdc 0.3A, 30Vdc 1A, 30Vac 0.5A 
resistive load; min. 1mA at 5Vdc; 500Vac insulated to the power port. 

 

Kontakt ist geschlossen wenn die DC-USV geladen und pufferbereit ist. 
Kontakt ist geschlossen wenn das Gerät im Pufferbetrieb ist. 
Kontakt ist geschlossen wenn ein Austauschen der Batterie erforderlich 
ist. 
Wenn eine Spannung > 10V anliegt ist eine Pufferung nicht möglich. 
Belastbarkeit der Relaiskontakte: max. 60Vdc 0.3A, 30Vdc 1A, 30Vac 
0.5A Widerstandslast;  min. 1mA bei 5Vdc;    isoliert mit 500Vac. 

 
 
 
 
 
 
 
 
 

Fig. 1 / Bild 1 

Fig. 2 / Bild 2 

Fig. 3 / Bild 3 

Ready

Charging

Buffering

ON
OFF

ON
OFF

ON
OFF

 

Overload

Replace 

Battery

Buffer time 

expired

Inhibit 

active

ON
OFF

ON
OFF

ON
OFF

ON
OFF

Wiring diagram / Anschlussdiagram UBC10.241 

24V 

unbuffered 

branch

 24V 

Power 

supply

+

-

N

L PE

DC-UPS 

UBC10.241

24V

IN

+

-

+

-

24V 

buffered 

branch

24V

OUT

Buffered 

load

+

-

Unbuffered 

load

+

-

 

 

Dimensions / Abmessungen

 

Functional Diagram / Funktionsschaltbild 

 

 

DC-UPS Control unit with integrated battery

Battery Charger

&

Tester

Cut-off 

Relay

24V 

Power 

Supply

Input

-

+

Reverse 

Polarity 

Protection

Input Fuse

&

*

(5)

(6)

Ready 

Contact

(1)

(2)

Buffering 

Contact

(3)

(4)

Electronic

Current

Limiter

Buffered

Load

+

-

Output

Controller

Diagnosis LED (yellow)

Check Wiring LED (red)

Status LED (green)

Buffer-time Limiter

10s, 30s, 1m, 3m, 10m,

Inhibit -

I

Replace 

Battery 

Contact

Step-up 

Converter

(7)
(8)

12V 5Ah battery

+

-

Fuse

 

*) Return current protection: This feature utilizes a MOSFET instead of a diode to minimize power losses.

 

PU-357.011.05-10C  (2016-02)

 