background image

 

8. Technical parameters 

 

Battery compartment 

7Ah / 12V 

Transformer compartment 

TRP: 20÷80VA, TRZ: 20÷80VA 

Tamper protection: 
- Pulling out the enclosure from 
RACK profiles 
- Enclosure opening 
- Patch Panel opening 

 
the C/NO terminals (C/NC closed housing), 
1A@30VDC/3A@250VAC 
the C/NO terminals (C/NC closed housing), 0,5A@30VDC/50VAC 
the C/NO terminals (C/NC closed housing), 0,5A@30VDC/50VAC 

PCB Signal Boards 
 

A/B Board 

– 8 signal lines - 30VDC/1,5A – 1 pair 

C/D Board 

– 8 signal lines - 30VDC/1,5A – 1 pair 

E/F Board 

– 8 signal lines - 30VDC/1,5A – 1 pair 

PCB Power Board 

230VAC/max.5A 

Mounting dimensions: 

W=19", H=2U 

Enclosure dimensions 

W=395, H=89, D=400 mm 

Net/gross weight:  

8,30 / 9,50 [kg] 

Finish:   

- steel plate 1 / 1,5mm, color black (RAL 9004)

 

Application: 

Indoor 

Notes: 

- The enclosure is mounted using the ARAS800/1000 rails  
  depending on the depth of the RACK 19" c 2xM6 screws 
butt mounted to RACK profiles 
- Patch Panel mounting 

– 4xM6 butt mounted to RACK pr 

2xM6  to ARAS800/1000 rails  
- The set includes: 

  pr

otective tube MM020 ø21/ø29 – 0,5m 

  protectiv

e tube MM064 ø6/ø10 – 0,5m 

  cable tie (black) 100x2,5 - 10 pieces 

  cable tie (black) 190x4,8 - 4 pieces 

  Six M6  cage nuts + plastic washer 

  2 M6  plastic washer 

Available accessories: 

MM020

 - protective tube 

ø21/ø29 – signal wires  

MM064

 - protective tube 

ø6/ø10 – for power cord 

ARAW45

 - fan  

AWZ618

 - 230VAC board with the F3,15A melting fuse 

transformers of the TRP/TRZ series: 20÷80VA 

Declarations, warranty 

CE, 2 years from the production date 

         
 
 

 
 

 
 
 

 
 

 
 

 

 
 

 
 

 

MANUFACTURER  

Pulsar  

Siedlec 150, 32-

744 Łapczyca 

Phone (+48) 14-610-19-40, Fax. (+48) 14-610-19-50 (+48) 14-610-19-50 

e-mail: 

biuro@pulsar.pl

sales@pulsar.pl

 

http:// 

www.pulsar.pl

www.zasilacze.pl

 

 
 

 

WARRANTY 

Pulsar (the manufacturer) grants a two-year quality warranty for the equipment, starting from the 

production date

 

 

Summary of Contents for ARAD-S2

Page 1: ... 7Ah battery transformer and the ARAW45 fan transformer and fan are not included Both ARAS800 and ARAS1000 rails selected depending on the depth of a RACK cabinet constitute the load bearing part of the enclosure not included The enclosure is fitted with 3 printed circuit boards PCB allowing connection of signal power and control cables Each of the boards has 8 pairs of terminals designed to opera...

Page 2: ...ile is properly adjusted Fig 2 3 Mounting of the ARAD S2 in the RACK 19 cabinet After mounting the ARAS rails in the rear of the RACK 19 mount the Patch Panel as shown in Figure 3 Fig 3 Mount the ARAD S2 enclosure on fully extended ARAS rails using 6xM4 screws complete with ARAS rails Tighten the screws from the inside Connect the Patch Panel wires as shown in the Fig 4 CAUTION Pay attention to th...

Page 3: ...64 Protective tube for signal cables 24 YTDY 6x0 5 wires internal external diameter ø21 ø29 available as accessory MM020 The routing of protective tubes in the Patch Panel and its sealing is shown in the Fig 5 Fig 5 The ARAD S2 enclosure is fitted with 3 tamper switches 1 Pulling out the enclosure from RACK profiles 2 Enclosure opening 3 Patch Panel opening The enclosure is mounted in the front of...

Page 4: ... PCB Power Board in a retractable housing PCB Signal Boards Single PCB Signal Board allows connecting up to 8 signal supply lines The maximum operating conditions of a single line 30VDC 1 5A PCB Signal Board in the Patch Panel PCB Signal Board in a retractable housing 5 Additional equipment Space for 7Ah battery TRP TRZ 20 80VA transformer ARAW45 fan 230VAC board with the F3 15A melting fuse ...

Page 5: ...8 and EVO192 ZX8 ZX4 PGM4 Modules 2x ZX8 ZX4 APR3 HUB2 and PGM4 1x APR3 ADM2 RISCO PRO24 EZ16 E04 EZ8 PRO116 128 140 Modules 2x EZ16 E04 EZ8 SATEL CA4V1 CA5 CA6 VERSA5 10 15 CA10 CA10E CA64E SM and MST1 INTEGRA 24 32 CA64E SM Modules CA64 PP EPS ADR O R O ROC O OC OPS OC OPS R OPS ROC VGM 16 SR and PTSA CA64E SM PYRONIX MATRIX 424 6 816 832 832 CROW RUNNER 4 8 TELMOR TCA 824 ROEL SIGMA 6 12 CERBER...

Page 6: ...00 rails depending on the depth of the RACK 19 cabinet 2xM6 screws butt mounted to RACK profiles Patch Panel mounting 4xM6 butt mounted to RACK profiles 2xM6 to ARAS800 1000 rails The set includes protective tube MM020 ø21 ø29 0 5m protective tube MM064 ø6 ø10 0 5m cable tie black 100x2 5 10 pieces cable tie black 190x4 8 4 pieces Six M6 screws cage nuts plastic washer 2 M6 screws plastic washer A...

Reviews: