AWZ637                                                     

 

 

8

 

 
3.2 Technical outputs

 

The PSU has indication outputs: 
 

 

EPS - absence of AC supply output

:  

- OC type output that indicates AC power loss. Under normal status, with 230 V supply, the output is connected 

to ground (L level 

– 0V). In case of power loss, the PSU will switch the output into high impedance state hi-

Z after approx. 10s. 

relay output indicating the absence of AC supply. In case of power loss, the PSU module will switch the relay 

contacts after approx.10 seconds. 

 
 

CAUTION!

 In Fig.2. the contact set in the potential-free status corresponds to a state with no AC 

power (AC power failure). 
 

 

 

PSU 

– technical output indicating absence of DC voltage at the PSU

-  OC type output indicating the PSU failure. In normal state (during correct operation) the output is connected 

to ground  (L  level 

– 0V). In case of absence of DC voltage at the output (e.g. short circuit), the output is 

switched into high impedance state 

– hi-Z. 

     - relay output. In case of a failure, the contacts of the relay change over. 

 
 

CAUTION!

  In  the  Fig.2.  the  set  of  contacts  shows  a  potential-free  status  of  the  relay  which 

corresponds to a state with no DC power (PSU failure). 

 

 

 

LoB 

– technical output indicating battery voltage

:  

- OC type output. Under normal status (U

BAT

 > 11,5 V) the output is connected to ground (L level 

– 0V). In case 

of decrease of battery voltage (U

BAT

 < 11,5 V) the output is switched into high impedance state 

– hi-Z. 

      -  relay output. In case of a battery voltage drop U

BAT

 < 11,5 V, the contacts of the relay change over. 

       The  power  supply  unit  does  not  feature  a  battery  detection  function.  In  the  case  of  no  battery  or  non  battery 

connected, the output is in the normal mode. 

 
 

CAUTION!

 In the Fig.2. the set of contacts shows a potential-free status of the relay which 

corresponds to a state with low battery level (U

BAT

 <11,5 V). 

 

 

Fig. 4. Electrical diagram of OC outputs.

 

 
4. Operation and use. 

 
4.1 Overload or short circuit of the PSU output (SCP on) 

In case of overload, the output voltage is automatically shut off, and so is the LED indicator. The restoration 

of the voltage takes place immediately after the failure (overload) is over. 
 

4.2 Battery-assisted operation.  

In case of a main power outage, the device is immediately switched into a battery-assisted operation. 

 
 
The  PSU  is  equipped  with  the  discharged  battery  disconnection  system.  During  the 

battery-assisted operation, reducing voltage below 9,5 V at the battery terminals will cause 
battery disconnection. 

 

 
 
 

Summary of Contents for AWZ637

Page 1: ...AWZ637 v 1 0 Enclosure with power supply unit dedicated to Dahua s Access Control EN Edition 1 from 15 05 2019 Supercedes ...

Page 2: ... PSU components and connectors 1 4 Specifications 2 Installation 2 1 Requirements 2 2 Installation procedure 3 Operating status indication 3 1 LED indication of operating status 4 Operation and use 4 1 Overload or short circuit of the PSU output SCP on 4 2 Disconnection of discharged battery 4 3 Maintenance 1 Technical description 1 1 General description A buffer PSU is intended for an uninterrupt...

Page 3: ...output indicating DC absence PSU failure relay type 6 LoB output indicating battery low voltage relay type 7 EPS AC absence technical output OC type 8 PSU output indicating DC absence PSU failure OC type 9 LoB output indicating battery low voltage OC type 10 VADJ potentiometer DC voltage adjustment 11 V V DC supply output 12 Battery connectors BAT red BAT black 13 LED indication on the front panel...

Page 4: ... 7 Fuse module LB4 Tab 2 Output terminals of the PSU Fig 2 The view of the PSU 1 4 Specifications electrical parameters tab 3 mechanical parameters tab 4 operation safety tab 5 operating parameters tab 6 Electrical parameters tab 3 PSU type 200 240 V 50 Hz Mains supply 1 1 A Current up to 100 W max Efficiency 80 Output voltage 11 13 8 V DC buffer operation 9 5 V 13 8 V DC battery assisted operatio...

Page 5: ...ff green normal status on failure off green normal status on failure off Technical outputs EPS output indicating AC power failure PSU output indicating DC absence PSU failure LoB output indicating battery low voltage relay type 1 A 30 V DC 50 V AC time lag approx 10s OC type 50mA max normal status L 0V level failure hi Z level time lag 10 s relay type 1 A 30 V DC 50 V AC OC type 50 mA max normal s...

Page 6: ...ng on ambient temperature 2 Installation 2 1 Requirements The buffer PSU shall be mounted by a qualified installer with appropriate permissions and qualifications for 230 V installations and low voltage installations required and necessary for a given country The device shall be mounted in confined spaces according to the environment class II with normal air humidity RH 90 max without condensation...

Page 7: ...y made and fully operational shock protection circuit is UNACCEPTABLE It can cause a device failure or an electric shock 3 Connect the controller to wire with DC plug 4 Connect the receivers wires to the AUX and COM connectors of the fuse module If necessary the values of fuses in the LB4 module can be selected but 1 5 A should not be exceeded 5 Connect the power 230 V 6 Connect the battery mind t...

Page 8: ... with no DC power PSU failure LoB technical output indicating battery voltage OC type output Under normal status UBAT 11 5 V the output is connected to ground L level 0V In case of decrease of battery voltage UBAT 11 5 V the output is switched into high impedance state hi Z relay output In case of a battery voltage drop UBAT 11 5 V the contacts of the relay change over The power supply unit does n...

Page 9: ...E LABEL Waste electrical and electronic equipment must not be disposed of with normal household waste According to the European Union WEEE Directive waste electrical and electronic equipment should be disposed of separately from normal household waste CAUTION The power supply unit is adapted for cooperation with the sealed lead acid batteries SLA After the operation period they must not be thrown ...