BLACKBOX 130 UL INSTRUCTION MANUAL
34
To program the BlackBox for this
Example,
proceed as follows.
Access the
Program Mode,
key in the
passcode
1997
and press
ENTER
Using the menu system access the parameters, as detailed below, and select
the relevant options and
ENTER
PARAMETER
SELECTED VALUE
P100 Mode
2 = Level
P101 Xducer
2 = dB6
P104 Measurement Units
4 = Feet
P105 Empty Distance
3.5
P106 Span
3.2
P210 Relay 1 Type
1 = Alarm
P211 R1 Function
1 = Level
P212 R1 ID
2 = High
P213 R1 Setpoint 1
8.5
P214 R1 Setpoint 2
8
P220 Relay 2 Type
1 = Alarm
P221 R2 Function
1 = Level
P222 R2 ID
4 = Low
P223 R2 Setpoint 1
1.0
P224 R2 Setpoint 2
1.5
Programming is now complete, and the unit can be returned to the run
mode, press
CANCEL
until
Run Mode?
Is displayed on the display press
ENTER
, and the BlackBox will return to the
Run Mode
.
Important Notice
The 4 to 20mA output will be automatically set to the value of P106 Span,
with 4mA being representative of 0% of Span (zero level) and 20mA 100%
of Span (Full level).