6.
Technical parameters
.
Parameters of DSO system (tab. 9).
Operation safety (tab. 10).
Operation parameters (tab. 11).
Table 9. Parameters of DSO system.
Functional class PN-EN 12101-10:2007
A
230 V / 400 V mains connection
Single-phase 230 V or
3-phase 3x230 V / 400 V 1)
Surge protection
type 3 (D) according to EN 61643-11 standard
Dimensions of RACK cabibnets
24U(600x600), 36U(600x600), 42U(600x600, 600x800),
45U (600x600, 600x800), 50U (600x800)
1)
Battery capacity
100..230Ah max
1)
Battery type
Sealed Lead-Acid (SLA) batteries (AGM, gel)
Status indication
panel for optical and acoustic indication., 60dB/1m; compliant with
EN54 16 standard
1)
Cooling
convection or forced cooling
1)
1)
Depending on DSO configuration.
Table 10. Operation safety.
Protection class EN 62368-1:2015-03 + AC1:2016-01
I (first)
Protection grade EN 60529: 2003
IP30
Electrical strength of insulation:
- between input (network) circuit and output circuits of PSU (I/P-O/P)
- between input circuit and protection circuit (I/P-FG)
- between output circuit and protection circuit (O/P-FG)
3000 V AC min.
1500 V AC min.
500 V AC min.
Insulation resistance:
- between input, output, and protective circuit
100 MΩ, 500 V DC
Table 11. Operating parameters.
Environmental class PN-EN 12101-10:2007
1
Operation temperature
-
5ºC...+40ºC
Storage temperature
-
25ºC...+60ºC
Relative humidity
20%...90%, no condensation
Sinusoidal vibrations during operation:
10
÷50Hz
50
÷150Hz
0,1g
0,5g
Surges during operation
0,5J
Direct insolation
unacceptable
Vibrations and surges during transport
Wg PN-83/T-42106