background image

www.pulsar.pl                                                      HADOC8012C                                                             

GREEN POWER plus

  

 

 

5

 

W

H

D

      

Electrical parameters (tab. 3) 

Mains supply 

176÷264V AC  

Current up to 

1,5A@230VAC  

Supply power 

120W max.  

Efficiency 

80% 

Output voltage 

11V÷ 13,8V DC – buffer operation 
9,5V÷ 13,8V DC – battery-assisted operation 

Output current t

AMB

<30°C 

8A + 0,5A battery charge - see chart 1 

Output current t

AMB

=40°C 

5,5A + 0,5A battery charge - see chart 1 

Voltage adjustment range 

12

÷14,5V DC 

Ripple 

150mV p-p max. 

Current consumption by PSU systems  

170 mA  

Battery charge current 

0,5A max. @ 17Ah (

± 5%)  

Short-circuit protection SCP 

electronic, automatic recovery 

Overload protection OLP 

105

÷150% of power supply, automatic recovery 

Battery circuit protection SCP and reverse 
polarity connection 

polymer fuse 

Surge protection 

varistors 

Overvoltage protection OVP 

 15,87-18,63V (automatic recovery) 

Excessive discharge protection UVP 

U<9,5V (

± 5%) – disconnect of connection battery 

Tampering protection system: 
- TAMPER 

– indicating unwanted opening of the 

PSU’s enclosure 

- a microswitch, NC contacts (enclosure closed) 
0,5A@50V DC (max.) 

LED indication:  
- AC diode indicating AC power status 
 
- AUX diode indicating DC power status at 
the PSU output 
 
- BAT diode indicating battery voltage level 

 
- red, normal status 

– on, failure: off 

 
- green, normal status 

– on, failure: off 

 
 
- green, normal status 

– on, failure: off 

Technical outputs: 

- FAC; output indicating AC power failure 

 
 
 
- FPS; output indicating DC absence/PSU failure 
 
 
 
- FLB output indicating battery low voltage 
 
 

 
- relay type: 1A@ 30VDC/50VAC, time lag: approx. 10s. 
- OC type, 50mA max., normal status: L (0V) level, 
failure: hi-Z level, time lag: 10s. 
 
- relay type: 1A@ 30VDC/50VAC, 
- OC type, 50mA max., normal status: L (0V) level, 
failure: hi-Z level  
 
- relay type: 1A@ 30VDC/50VAC, 
- OC type, 50mA max., normal status: (U

BAT

 >11,5V): L 

(0V) level, 
 failure: (U

BAT

 <11,5V): hi-Z level 

 
     Mechanical parameters (tab. 4) 

Enclosure dimensions 

285 x 297 x 80+8  [mm] (WxHxD) 

Fixation 

See figure 3 

Fitting battery 

17Ah/12V (SLA) max. 
180x120x75mm (WxHxD) max  

Net/gross weight 

2,6kg / 2,8kg 

Enclosure  

Steel plate, DC01 0,7mm colour: RAL 9003 

Closing 

Cheese head screw x 2 (at the front),  (lock assembly possible) 

Connectors 

Power supply: 

Φ0,63-2,50 (AWG 22-10) 

Outputs: Φ0,63-2,50 (AWG 22-10),  
battery output BAT: 6,3F-2,5  
TAMPER output: wires  

Notes 

The enclosure does not adjoin the assembly surface so that cables can be led. 

       
    

Operation safety (tab.5) 

Protection class PN-EN 60950-1:2007 

I (first) 

Protection grade PN-EN 60529: 2002 (U) 

IP20 

Electrical strength of insulation: 
- between input and output circuits of the PSU (I/P-O/P) 
- between input circuit and PE protection circuit (I/P-FG) 
- between output circuit and PE protection circuit (O/P-FG) 

 
3000 V/AC min. 
1500 V/AC min. 
  500 V/AC min. 

Insulation resistance: 
- between input circuit and output or protection circuit 

 
100 MΩ, 500V/DC  

Summary of Contents for HADOC 8012C

Page 1: ...HADOC 8012C v 1 0 HADOC 13 8V 8A 17Ah OC Buffer switch mode power supply unit with technical outputs EN Edition 3 from 10 10 2014 Supercedes edition 2 from 05 06 2014 GREEN POWER plus ...

Page 2: ...sted operation 4 3 Maintenance 1 Technical description 1 1 General description A buffer PSU is intended for uninterrupted supply to devices that require stabilised voltage of 12V DC 15 The PSU provides voltage of U 13 8V DC with output current of I 8A 0 5A for battery charge In case of power decay a battery back up is activated immediately The PSU is constructed based on the switch mode PSU with h...

Page 3: ...nd connectors Table 1 Elements of the module s see fig 2 Element no Description 1 LED indicating presence of AC power 2 LED indicating presence of DC power 3 LED indicating correct battery voltage 4 FAC AC absence technical output relay type 5 FPS output indicating DC absence PSU failure relay type 6 FLB output indicating battery low voltage relay type 7 FAC AC absence technical output OC type 8 F...

Page 4: ...ents and connectors tab 2 fig 3 lement no Fig 3 Description 1 PSU module 2 TAMPER contact sabotage protection NC Tab 2 Output terminals of the PSU Fig 3 The view of the PSU 1 4 Specifications electrical parameters tab 3 mechanical parameters tab 4 operation safety tab 5 operating parameters tab 6 ...

Page 5: ...ff green normal status on failure off Technical outputs FAC output indicating AC power failure FPS output indicating DC absence PSU failure FLB output indicating battery low voltage relay type 1A 30VDC 50VAC time lag approx 10s OC type 50mA max normal status L 0V level failure hi Z level time lag 10s relay type 1A 30VDC 50VAC OC type 50mA max normal status L 0V level failure hi Z level relay type ...

Page 6: ...tional air flow through ventilating holes of the enclosure Before installation prepare a PSU load balance During normal operation the total current drawn by the device may not exceed I 8A Maximum battery charge current 0 5A Total device current battery 8 5A max As the PSU is designed for a continuous operation and is not equipped with a power switch therefore an appropriate overload protection sha...

Page 7: ...normal status AC power permanently illuminated AC power absence is indicated by the AC diode going out Caution LED indicates power absence if the outage lasts 10s green LED Fig 2 element 2 indicates DC power at the PSU output Under normal status the diode is permanently illuminated In case of a short circuit or an overload the diode is off green LED Fig 2 element 3 indicates battery voltage level ...

Page 8: ...Overload or short circuit of the PSU output SCP on In case of overload the output voltage is automatically shut off and so is the LED indicator The restoration of the voltage takes place immediately after the failure overload is over 4 2 Battery assisted operation In case of a main power outage the device is immediately switched into a battery assisted operation The PSU is equipped with the discha...

Page 9: ...www pulsar pl HADOC8012C GREEN POWER plus 9 ...

Page 10: ... later that within 14 days from the delivery to the service centre of the manufacturer 6 The repair period mentioned in item 5 may be prolonged if there are no technical possibilities to carry out the repairs or if the equipment has been conditionally accepted due to the breaking warranty terms by the claimant 7 All the services rendered by force of the warranty are carried out at the service cent...

Reviews: