www.pulsar.pl                                                      HADOC8012C                                                             

GREEN POWER plus

  

 

 

7

 

RED LED: 

 

on 

– the PSU is supplied with 230V AC  

 

off 

– no 230V AC supply  

 

GREEN LED: 

 

on 

– DC voltage in the AUX output of the PSU 

 

off 

– no DC voltage in the AUX output of the PSU 

 

on 

– PSU’s voltage U

BAT

 > 11,5V 

 

off 

– PSU’s voltage U

BAT

 < 11,5V 

 

 

 
 

 

The  shock  protection  circuit  shall  be  performed  with  a  particular  care,  i.e.  the  yellow  and 
green wire coat of the power cable shall stick to one side of the terminal - marked with  

 symbol on the PSU enclosure. Operation of the PSU without the properly made and fully 

operational shock protection circuit is UNACCEPTABLE! It can cause a device failure or an 
electric shock. 

 

4. Connect the 

receivers’ cables to the terminals V+ (+), V-(-) of the PSU module.  

5. Connect the power (~230V) 
6. Check the PSU output voltage: 
- the PSU voltage without load should amount to U=13,8V DC.   
7. Connect the battery (mind the colours):   
- battery output (+V):  BAT+ cable / red, 
- battery output (0V):  BAT 

– cable / GND / black. 

8. Check the optical indication of the PSU status: LED (green LED on the power supply module). 
9. After installing and checking proper working, the enclosure can be closed. 
 

3. Operating status indication. 

 
3.1 LED indication of operating status. 

The PSU is equipped with 3 diodes on the front panel:

 

 
 

 

 
 

 

Moreover, the PSU is equipped with 3LEDs on the PCB board:

 

 - red LED (Fig.2, element 1) normal status (AC power): permanently illuminated. AC power absence is 
indicated by the AC diode going out.  
Caution! LED indicates power absence if the outage lasts >10s. 

 

-  green  LED  (Fig.2,  element  2)  indicates  DC  power  at  the  PSU  output.  Under  normal  status  the  diode  is 
permanently illuminated. In case of a short circuit or an overload, the diode is off. 
 
- green LED  (Fig.2, element 3) indicates battery voltage level. Under normal status (U

BAT

 > 11,5V) the diode is 

permanently illuminated. In case of decrease of battery voltage (U

BAT

 < 11,5V) the diode is off.

 

 

3.2 Technical outputs 

The PSU has indication outputs: 
 

 

FAC - absence of AC supply output

:  

- OC type output that indicates AC power loss. Under normal status, with 230V AC supply, the output is connected to 

ground (L level 

– 0V). In case of power loss, the PSU will switch the output into high impedance state hi-Z after 

approx. 10s. 

relay  output  indicating  the  absence  of  AC  supply.  In  case  of  power  loss,  the  PSU  module  will  switch  the  relay 

contacts after approx. 10 seconds. 

 

CAUTION!

 In Fig.2. the contact set in the potential-free status corresponds to a state with no AC 

power (AC power failure). 
 
 

 

FPS 

– technical output indicating absence of DC voltage at the PSU

-    OC  type  output  indicating  the  PSU  failure.  In  normal  state  (during  correct  operation)  the  output  is  connected  to 

ground (L level 

– 0V). In case of absence of DC voltage at the output (e.g. short circuit), the output is switched 

into high impedance state 

– hi-Z. 

      - relay output. In case of a failure, the contacts of the relay change over. 
 
 

Summary of Contents for HADOC 8012C

Page 1: ...HADOC 8012C v 1 0 HADOC 13 8V 8A 17Ah OC Buffer switch mode power supply unit with technical outputs EN Edition 3 from 10 10 2014 Supercedes edition 2 from 05 06 2014 GREEN POWER plus ...

Page 2: ...sted operation 4 3 Maintenance 1 Technical description 1 1 General description A buffer PSU is intended for uninterrupted supply to devices that require stabilised voltage of 12V DC 15 The PSU provides voltage of U 13 8V DC with output current of I 8A 0 5A for battery charge In case of power decay a battery back up is activated immediately The PSU is constructed based on the switch mode PSU with h...

Page 3: ...nd connectors Table 1 Elements of the module s see fig 2 Element no Description 1 LED indicating presence of AC power 2 LED indicating presence of DC power 3 LED indicating correct battery voltage 4 FAC AC absence technical output relay type 5 FPS output indicating DC absence PSU failure relay type 6 FLB output indicating battery low voltage relay type 7 FAC AC absence technical output OC type 8 F...

Page 4: ...ents and connectors tab 2 fig 3 lement no Fig 3 Description 1 PSU module 2 TAMPER contact sabotage protection NC Tab 2 Output terminals of the PSU Fig 3 The view of the PSU 1 4 Specifications electrical parameters tab 3 mechanical parameters tab 4 operation safety tab 5 operating parameters tab 6 ...

Page 5: ...ff green normal status on failure off Technical outputs FAC output indicating AC power failure FPS output indicating DC absence PSU failure FLB output indicating battery low voltage relay type 1A 30VDC 50VAC time lag approx 10s OC type 50mA max normal status L 0V level failure hi Z level time lag 10s relay type 1A 30VDC 50VAC OC type 50mA max normal status L 0V level failure hi Z level relay type ...

Page 6: ...tional air flow through ventilating holes of the enclosure Before installation prepare a PSU load balance During normal operation the total current drawn by the device may not exceed I 8A Maximum battery charge current 0 5A Total device current battery 8 5A max As the PSU is designed for a continuous operation and is not equipped with a power switch therefore an appropriate overload protection sha...

Page 7: ...normal status AC power permanently illuminated AC power absence is indicated by the AC diode going out Caution LED indicates power absence if the outage lasts 10s green LED Fig 2 element 2 indicates DC power at the PSU output Under normal status the diode is permanently illuminated In case of a short circuit or an overload the diode is off green LED Fig 2 element 3 indicates battery voltage level ...

Page 8: ...Overload or short circuit of the PSU output SCP on In case of overload the output voltage is automatically shut off and so is the LED indicator The restoration of the voltage takes place immediately after the failure overload is over 4 2 Battery assisted operation In case of a main power outage the device is immediately switched into a battery assisted operation The PSU is equipped with the discha...

Page 9: ...www pulsar pl HADOC8012C GREEN POWER plus 9 ...

Page 10: ... later that within 14 days from the delivery to the service centre of the manufacturer 6 The repair period mentioned in item 5 may be prolonged if there are no technical possibilities to carry out the repairs or if the equipment has been conditionally accepted due to the breaking warranty terms by the claimant 7 All the services rendered by force of the warranty are carried out at the service cent...