1.4. Specifications: 

- electrical specifications (tab.3) 
- mechanical specifications (tab.4) 
- operation safety (tab.5) 
- operating specifications (tab.6)

 

 
Electrical specifications (tab. 3). 

Mains supply 

230V AC (-15%/+10%) 

Current consumption 

1,1A  

Power frequency 

50Hz 

PSU power 

138W  

Efficiency 

71% 

Output voltage 

11,0V ÷ 13,8V DC – buffer operation 
10,0V ÷ 13,8V DC – battery-assisted operation 

Output current 

10A (without a battery), AUX output 
9,3A + 0,7A battery charge 
7,9A + 2,1A battery charge 
6,4A + 3,6A battery charge  
5,2A + 4,8A battery charge 
 

 

or 

3 x 2,5A – outputs : +AUX1-, +AUX2-, +AUX3- 

Output voltage escalation, decrease, and 
keeping time 

20ms / 30ms  /50ms 
 

Output voltage adjustment range 

12,0V ÷ 14,5V DC  

Ripple voltage  

50mV p-p max. 

Current drawn by the PSU systems 

20mA max. – battery-assisted operation 

Battery charging current 

0,7A / 2,1A / 3,6A / 4,8A - I

BAT 

(J1, J2) jumper selectable 

Short-circuit protection SCP  

200% ÷ 250% of the PSU power,  
hiccup mode– 13A/200ms and/or  
fuse damage in the battery circuit (fuse-element replacement 
required) 

Overload protection OLP 

110% ÷ 150% of the PSU power – electronic. 
Disconnection of the PSU outputs – automatic return after DC 
output circuit disconnection 

Over voltage protection OVP  

U>16,5V, disconnection of the output voltage, automatic return 
(AUX+ disconnection) 

Battery circuit protection SCP and reverse 
polarity connection 

10A – current limiting, F

BAT 

fuse (failure requires fuse-element 

replacement) 

Deep discharge protection UVP 

U < 10,0V (± 5%) – battery disconnection (-BAT), 
P

BAT 

jumper selectable 

Sabotage protection: 
- TAMPER output indicating enclosure opening 

 
- micro-switches x2, NC contacts (enclosure closed and fixed to the 
surface), 0,5A@50V DC (max.) 

Technical outputs: 
- FAC; output indicating AC power failure 
 
- FPS; technical output of the PSU operation 
status  

 
- type OC, 50mA max. normal status: L (0V) level, failure: hi-Z level, 
relay: 10s. 
- type OC, 50mA max. normal status: L (0V) level, failure: hi-Z level 
(automatic return after restoration of correct operation) 

F

BAT 

fuse

 

F

MAIN 

fuse 

T 10A / 250V 
T 6,3A / 250V  

             
 

Mechanical specifications (tab. 4). 

Enclosure dimensions 

405 x 445 x 178  (400 x 440 x 170+8) (WxHxD) [mm] (+/- 2) 

Fixing 

370 x 410 x Φ 6   x 4 (WxH)   

Fitting battery 

65Ah / 12V (SLA) max.  

Net/gross weight 

11,20 / 12,10 kg 

Enclosure 

Steel plate DC01 1,2mm thick, colour: RAL 9003 

Closing 

Cheese head screw x2 (at the front), lock assembly possible 

Connectors 

Supply: Φ0,41-2,5 
Outputs: Ф0,41÷2,5 
BAT battery outputs: connectors: Φ6 (M6-0-2,5) 
TAMPER output: leads 

Notes 

The enclosure does not adjoin the assembly surface so that cables can be led. 
Convectional cooling. 

Summary of Contents for PSBS 10A12E

Page 1: ...PSBS 10A12E v 1 0 PSBS 13 8V 10A 65Ah Buffer switched mode power supply unit EN Edition 3 from 16 09 2013 Supersedes the edition 2 from 18 09 2012 ...

Page 2: ...ration and use 4 1 Overload or short circuit of the PSU output 4 2 Battery assisted operation 4 3 Maintenance 1 Technical description 1 1 General description A buffer PSU is intended for an uninterrupted supply to alarm system devices requiring stabilized voltage of 12V DC 15 The PSU provides voltage of 13 8 V DC with current efficiency of 1 Output current 10A without a battery 2 Output current 9 ...

Page 3: ...er power supply unit PSBS 13 8V 3x5V 7 4V 12x0 5A 65Ah PSBS 10A12E 3xDCDC20 5V 7 4V 2A 3xLB4 12x0 5A AWZ574 or AWZ576 65Ah 1 2 Block diagram fig 1 Fig 1 Block diagram of the PSU 1 3 Description of PSU components and connectors tab 1 tab 2 fig 2 fig 3 Table 1 Element no Fig 2 Description 1 FBAT fuse in the battery circuit 2 START button launching the PSU from a battery 3 PBAT pin configuration of t...

Page 4: ...ack 12 FAC AC absence technical output OC type open collector hi Z level status AC power failure L level status AC supply 13 FPS technical output of the PSU operation status OC type open collector hi Z level status failure L level status correct operation 14 LED indication connector Tab 1 Element of the PSU pcb see fig 2 Fig 2 The view of the PSU pcb ...

Page 5: ...ion transformer 2 PSU board tab 1 3 TAMPER micro switch contacts of tamper resistance NC 4 FMAIN fuse in the supply circuit 230 V AC 5 L N 230 V AC power connector PE PE connector 6 Battery connectors BAT red BAT black Tab 2 PSU components see fig 3 Fig 3 The view of the PSU ...

Page 6: ...tion Over voltage protection OVP U 16 5V disconnection of the output voltage automatic return AUX disconnection Battery circuit protection SCP and reverse polarity connection 10A current limiting FBAT fuse failure requires fuse element replacement Deep discharge protection UVP U 10 0V 5 battery disconnection BAT PBAT jumper selectable Sabotage protection TAMPER output indicating enclosure opening ...

Page 7: ...urrent 9 3A 0 7A battery charge 3 Output current 7 9A 2 1A battery charge 4 Output current 6 4A 3 6A battery charge 5 Output current 5 2A 4 8A battery charge Total current of the receivers battery 10A max As the PSU is designed for a continuous operation and is not equipped with a power switch therefore an appropriate overload protection shall be guaranteed in the power supply circuit Moreover the...

Page 8: ... diode is permanently illuminated The absence of AC supply is indicated by the AC diode going out LB red diode indicates the battery charging process the intensity of illumination is dependent on the charging current AUX green diode indicates the DC supply status at the output of the PSU Under normal status the diode is permanently illuminated In case of a short circuit or on overload the diode is...

Page 9: ...the PSU power or reverse battery connection the FBAT fuse in the battery circuit becomes permanently damaged and the restoration of the voltage at the BAT output requires the replacement of the fuse 4 2 Battery assisted operation In case of the main power outage the device is immediately switched into a battery assisted operation In order to run the PSU from the battery only connect the BAT connec...

Page 10: ...that within 14 days from the delivery to the service centre of the manufacturer 6 The repair period mentioned in item 5 may be prolonged if there are no technical possibilities to carry out the repairs or if the equipment has been conditionally accepted due to the breaking warranty terms by the claimant 7 All the services rendered by force of the warranty are carried out at the service centre of t...

Reviews: