PSBS10A12E 

 

 

 

 

 
 

 

4. Operation and use. 
 

4.1 Overload or short circuit of the PSU output  

The output circuit of the PSU is equipped with the electronic current protection. If the output voltage value 

exceeds the acceptable threshold – Imax, the PSU output will be disconnected. The disconnection will be indicated 
by the  O1, O2, O3 and AUX  diodes going out. Reactivation of the voltage will be automatic after disconnecting the 
receivers from the output. 

Additionally, the AUX1, AUX2, AUX3 outputs are protected separately, with the use of PTC polyswitches. If 

the load exceeds 2,5A, there will be an automatic disconnection of the output voltage indicated by the O1, O2 or 
O3 green diode going out. Restoring of the output voltage requires cutting off the output load for at least 1 minute. 

In case of a short circuit at the AUX, BAT output (load: 200% ÷ 250% of the PSU power) or reverse battery 

connection, the F

BAT

 fuse in the battery circuit becomes permanently damaged and the restoration of the voltage at 

the BAT output requires the replacement of the fuse. 

 

 

4.2 Battery-assisted operation. 

 

In case of the main power outage, the device is immediately switched into a battery-assisted operation. 
In order to run the PSU from the battery only, connect the BAT connectors in accordance with the signs:  

+ BAT red to ‘plus’ and, - BAT black to 'minus’ then press the START button on the main board and hold it for 5 
seconds. 

 

 

The PSU is equipped with the discharged battery disconnection system (UVP), configured by 
the P

BAT 

jumper. The protection mode is off when the P

BAT

 jumper is removed. 

 

4.3 Maintenance

  

 
Any and all maintenance operations may be performed following the disconnection of the PSU from the 

power supply network. The PSU does not require performing any specific maintenance measures. However, in 
case of dust, clean the interior with compressed air. In case of fuse replacement, use a replacement of the same 
parameters. 

 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

Summary of Contents for PSBS 10A12E

Page 1: ...PSBS 10A12E v 1 0 PSBS 13 8V 10A 65Ah Buffer switched mode power supply unit EN Edition 3 from 16 09 2013 Supersedes the edition 2 from 18 09 2012 ...

Page 2: ...ration and use 4 1 Overload or short circuit of the PSU output 4 2 Battery assisted operation 4 3 Maintenance 1 Technical description 1 1 General description A buffer PSU is intended for an uninterrupted supply to alarm system devices requiring stabilized voltage of 12V DC 15 The PSU provides voltage of 13 8 V DC with current efficiency of 1 Output current 10A without a battery 2 Output current 9 ...

Page 3: ...er power supply unit PSBS 13 8V 3x5V 7 4V 12x0 5A 65Ah PSBS 10A12E 3xDCDC20 5V 7 4V 2A 3xLB4 12x0 5A AWZ574 or AWZ576 65Ah 1 2 Block diagram fig 1 Fig 1 Block diagram of the PSU 1 3 Description of PSU components and connectors tab 1 tab 2 fig 2 fig 3 Table 1 Element no Fig 2 Description 1 FBAT fuse in the battery circuit 2 START button launching the PSU from a battery 3 PBAT pin configuration of t...

Page 4: ...ack 12 FAC AC absence technical output OC type open collector hi Z level status AC power failure L level status AC supply 13 FPS technical output of the PSU operation status OC type open collector hi Z level status failure L level status correct operation 14 LED indication connector Tab 1 Element of the PSU pcb see fig 2 Fig 2 The view of the PSU pcb ...

Page 5: ...ion transformer 2 PSU board tab 1 3 TAMPER micro switch contacts of tamper resistance NC 4 FMAIN fuse in the supply circuit 230 V AC 5 L N 230 V AC power connector PE PE connector 6 Battery connectors BAT red BAT black Tab 2 PSU components see fig 3 Fig 3 The view of the PSU ...

Page 6: ...tion Over voltage protection OVP U 16 5V disconnection of the output voltage automatic return AUX disconnection Battery circuit protection SCP and reverse polarity connection 10A current limiting FBAT fuse failure requires fuse element replacement Deep discharge protection UVP U 10 0V 5 battery disconnection BAT PBAT jumper selectable Sabotage protection TAMPER output indicating enclosure opening ...

Page 7: ...urrent 9 3A 0 7A battery charge 3 Output current 7 9A 2 1A battery charge 4 Output current 6 4A 3 6A battery charge 5 Output current 5 2A 4 8A battery charge Total current of the receivers battery 10A max As the PSU is designed for a continuous operation and is not equipped with a power switch therefore an appropriate overload protection shall be guaranteed in the power supply circuit Moreover the...

Page 8: ... diode is permanently illuminated The absence of AC supply is indicated by the AC diode going out LB red diode indicates the battery charging process the intensity of illumination is dependent on the charging current AUX green diode indicates the DC supply status at the output of the PSU Under normal status the diode is permanently illuminated In case of a short circuit or on overload the diode is...

Page 9: ...the PSU power or reverse battery connection the FBAT fuse in the battery circuit becomes permanently damaged and the restoration of the voltage at the BAT output requires the replacement of the fuse 4 2 Battery assisted operation In case of the main power outage the device is immediately switched into a battery assisted operation In order to run the PSU from the battery only connect the BAT connec...

Page 10: ...that within 14 days from the delivery to the service centre of the manufacturer 6 The repair period mentioned in item 5 may be prolonged if there are no technical possibilities to carry out the repairs or if the equipment has been conditionally accepted due to the breaking warranty terms by the claimant 7 All the services rendered by force of the warranty are carried out at the service centre of t...