3. Connect the batteries with the battery wires paying attention to the polarity (+ BAT red, -BAT black) and the numbering 
of wires. 
4. Mount the batteries paying attention to the correct order (See Fig. 1). 
5. Close the front panel, screw the locking screws. 
6. Make connections between batteries using outputs at the front panel, depending on the application (see Figure 4) and 
connect them to the uninterruptible power supply with appropriate protection systems and a charging circuit control 
system.  
7. Close the enclosure, cabinet, etc. once the tests and operation control is completed. 
 
 

Due to the risk of combustible gas generation during charging, the RACK cabinet and the 
mounting space must be properly ventilated.  

 
 

 

 

Fig. 5. Methods to connect batteries. 

3. Maintenance. 

The PSU does not require any specific maintenance; however, it should be cleaned with compressed air if used 

in dusty conditions.  

 
 

                          

WEEE LABEL 

 

Waste electrical and electronic equipment must not be disposed of with normal household waste. 

According to the European Union WEEE Directive, waste electrical and electronic equipment should 

be disposed of separately from normal household waste

.

 

 

 

The power supply unit is adapted for a sealed lead-acid battery (SLA). After the operation period it must not be disposed of but recycled according to the 

applicable law.

 

 

 

 
 
 
 
 
 
 
 
 
 
 
 