background image

www.pulsar.pl

    

 

 

 

ROUPS12VR   

 

 

RACK POWER CCTV

 

 

about 20s.) 

Battery circuit protection SCP and reverse  
polarity connection 

polymer fuse PTC 

Surge protection 

varistors 

Excessive discharge protection UVP 

U<9,5V (+/-5%) – disconnect of connection battery 

Optical indication of operation: 

LED: AC, DC, TEMP, LoB, ALARM, DVR 

Acoustic operation indication: 

Piezoelectric indicator ~75dB/0,3m 

The ALARM technical output of collective 
failure 

Relay type: 1A@ 30VDC/50VAC 

The F

MAINS

 fuse in the 230V power supply 

circuit  

T 3,15A 

F

DVR

 fuses in the recorder power supply 

circuits AUX(+) 

F 5A 

      

Mechanical parameters (tab. 3). 

Enclosure dimensions 

W=19”, H=2U; 482 x 88 x 223  mm (WxHxD) 

Fixation 

four-point butt mounting to RACK profiles – the set include 4 M6  cage nuts 

Net weight 

5,50kg / 5,80kg 

Enclosure 

Steel plate RAL 9005, black 

Connectors 

230V AC input: the IEC C14 socket with a fuse, power cable 2m  
(included) 
Outputs: ALARM, BAT: 

Φ

0,5-2,1 (AWG 24-12) 0,5-1,5mm

Output DVR: 

Φ

0,5-2,1 (AWG 24-12) 0,5-1,5mm

2

, power cable 2m  

(included) 
Battery output BAT: 6,3F-2,5 

Notes 

Forced cooling (fan). 

       Operation safety (tab.4). 

Protection class PN-EN 60950-1:2007 

I (first) 

Protection grade PN-EN 60529: 2002 (U) 

IP20 

Electrical strength of insulation: 
- between input and output circuits of the PSU (I/P-O/P) 
- between input circuit and PE protection circuit (I/P-FG) 
- between output circuit and PE protection circuit (O/P-FG) 

 
3000 V/AC min. 
1500 V/AC min. 
  500 V/AC min. 

Insulation resistance: 
- between input circuit and output or protection circuit 

 
100 M

, 500V/DC  

Operating parameters (tab.5). 

Environmental class 

II 

Operating temperature 

-10ºC...+45ºC 

Storage temperature 

-20ºC...+60ºC 

Relative humidity 

20%...90%, without condensation 

Vibrations during operation 

unacceptable 

Impulse waves during operation 

unacceptable 

Direct insulation 

unacceptable 

Vibrations and impulse waves during transport 

According to PN-83/T-42106 

 

 
2.  Installation. 
 

2.1.  Requirements. 
The PSU RACK shall be mounted by a qualified installer with appropriate permissions and qualifications for 

230V/AC installations and low-voltage installations (required and necessary for a given country). The device shall 
be  mounted  in  confined  spaces,  according  to  the  environment  class  II,  with  normal  air  humidity  (RH=90%  max. 
without condensation) and the temperature from -10°C do +45°C.  

 During normal operation the total current consumption of the receivers cannot exceed 

I=5A. Maximum battery charging current is: 1A.  

Total device c battery: 6A. 

 

Summary of Contents for ROUPS12VR

Page 1: ...ROUPS12VR v 1 0 ROUPS 12V 5A RACK mounted buffer power supply of the recorder EN Edition 1 from 15 03 2016 Supercedes the edition ...

Page 2: ... failure relay type activated by 230V AC power loss low voltage of the PSU 11 5V activation of the output fuse too high temperature of the PSU 70 C the PSU failure protections SCP short circuit protection OVP overvoltage protection overvoltage protection overload protection OLP forced cooling fan warranty 2 year from the production date Sample application of the RACK power supply unit CONTENTS 1 T...

Page 3: ...osure adapted for mounting in standard RACK 19 cabinets 1 2 Block diagram Fig 1 The block diagram of the PSU 1 3 Description of PSU components and connectors Table 1 Elements of the PSU Element no Fig 2 Description AC OK green LED indicating the presence of 230V voltage DC OK green LED indicating the presence of DC voltage TEMP red LED indicating too high temperature of the power supply 70 C LoB r...

Page 4: ... 2 Mains supply 176 264V AC Current up to 0 8A 230V AC max Supply power 74W max Efficiency 71 Output voltage DVR recorder 12V DC Output current 5A recorder 1A battery charge Ripple 50 mV p p max Battery charge current 1A max 5 Short circuit protection SCP F 5A melting fuse Overload protection OLP Current consumption by PSU systems 105 150 of the PSU power automatic return 0 2A Overvoltage protecti...

Page 5: ...rst Protection grade PN EN 60529 2002 U IP20 Electrical strength of insulation between input and output circuits of the PSU I P O P between input circuit and PE protection circuit I P FG between output circuit and PE protection circuit O P FG 3000 V AC min 1500 V AC min 500 V AC min Insulation resistance between input circuit and output or protection circuit 100 MΩ 500V DC Operating parameters tab...

Page 6: ... the following technical connections can be made ALARM technical output of collective failure 5 Connect the battery to the BAT terminals battery output V terminal BAT battery output V terminal BAT 6 Connect the 230V AC power cord with the IEC C13 plug included to the 230V AC power supply and turn on the power 230V 7 Check the PSU operation indicator 3 Operating status indication 3 1 LED indication...

Page 7: ... the ON OFF position of the switch switch in the up position indication ON switch in the down position indication OFF 4 Operation and use 4 1 Overload or short circuit of the PSU output The power supply outputs are protected against short circuit by melting fuse in the case of fuse failure it should be replaced with a fuse of the same type 4 2 Battery assisted operation In case of a main power out...

Page 8: ...e are no technical possibilities to carry out the repairs or if the equipment has been conditionally accepted due to the breaking warranty terms by the claimant 7 All the services are carried out at the service centre of the manufacturer exclusively 8 The warranty does not cover the defects of the equipment resulting from reasons beyond the manufacturer s control mechanical damage improper storage...

Reviews: