ROUPS12VR   

 

 

RACK POWER CCTV

 

 

 

3.2.  Technical output. 
 
The power supply is fitted with the  ALARM output of collective failure (relay type). A collective failure can 

be triggered by the following events: 

- 230V AC mains power failure 
- Melting fuse activation F

DVR

 

- Failure of the switch mode power supply 
-Too high temperature of the switch mode power supply (>70°C) 
- Low battery voltage (<11,5V) 
 

 

 

Fig. 4. Electrical diagram of the ALARM collective output of failure. 

 

 
CAUTION!  In  Fig.4  the  set  of  contacts  shows  a  potential-free  status  of  the  relay,  which 
corresponds to power supply failure. 

 

 

 

3.3.  Acoustic indication. 
A collective failure is indicated by the piezoelectric indicator, 1 beep every second. The acoustic indication 

can be turned off by changing the ON / OFF position of the switch   . 
 

                                                       

 switch in the up position, indication ON 

 switch in the down position, indication OFF 

 
4.  Operation and use. 
 

4.1.  Overload or short circuit of the PSU output. 
The power supply outputs are protected against short circuit by melting fuse; in the case of fuse failure, it 

should be replaced with a fuse of the same type.  

 
4.2.  Battery-assisted operation. 
In case of a main power outage, the device is immediately switched into a battery-assisted operation.  
 

 
The  PSU  is  equipped  with  the  discharged  battery  disconnection  system.  During 

the  battery-assisted  operation,  reducing  voltage  below  9,5V  at  the  battery  terminals  will 
cause battery disconnection. 
 

 

4.3.  Maintenance. 
Any  and  all  maintenance  operations  may  be  performed  following  the  disconnection  of  the  PSU  from  the 

power supply network. The PSU   does not require performing any specific maintenance measures. In case of fuse 
replacement, use a replacement of the same parameters. 

 
 
 
 
 
 
 
 
 

Summary of Contents for ROUPS12VR

Page 1: ...ROUPS12VR v 1 0 ROUPS 12V 5A RACK mounted buffer power supply of the recorder EN Edition 1 from 15 03 2016 Supercedes the edition ...

Page 2: ... failure relay type activated by 230V AC power loss low voltage of the PSU 11 5V activation of the output fuse too high temperature of the PSU 70 C the PSU failure protections SCP short circuit protection OVP overvoltage protection overvoltage protection overload protection OLP forced cooling fan warranty 2 year from the production date Sample application of the RACK power supply unit CONTENTS 1 T...

Page 3: ...osure adapted for mounting in standard RACK 19 cabinets 1 2 Block diagram Fig 1 The block diagram of the PSU 1 3 Description of PSU components and connectors Table 1 Elements of the PSU Element no Fig 2 Description AC OK green LED indicating the presence of 230V voltage DC OK green LED indicating the presence of DC voltage TEMP red LED indicating too high temperature of the power supply 70 C LoB r...

Page 4: ... 2 Mains supply 176 264V AC Current up to 0 8A 230V AC max Supply power 74W max Efficiency 71 Output voltage DVR recorder 12V DC Output current 5A recorder 1A battery charge Ripple 50 mV p p max Battery charge current 1A max 5 Short circuit protection SCP F 5A melting fuse Overload protection OLP Current consumption by PSU systems 105 150 of the PSU power automatic return 0 2A Overvoltage protecti...

Page 5: ...rst Protection grade PN EN 60529 2002 U IP20 Electrical strength of insulation between input and output circuits of the PSU I P O P between input circuit and PE protection circuit I P FG between output circuit and PE protection circuit O P FG 3000 V AC min 1500 V AC min 500 V AC min Insulation resistance between input circuit and output or protection circuit 100 MΩ 500V DC Operating parameters tab...

Page 6: ... the following technical connections can be made ALARM technical output of collective failure 5 Connect the battery to the BAT terminals battery output V terminal BAT battery output V terminal BAT 6 Connect the 230V AC power cord with the IEC C13 plug included to the 230V AC power supply and turn on the power 230V 7 Check the PSU operation indicator 3 Operating status indication 3 1 LED indication...

Page 7: ... the ON OFF position of the switch switch in the up position indication ON switch in the down position indication OFF 4 Operation and use 4 1 Overload or short circuit of the PSU output The power supply outputs are protected against short circuit by melting fuse in the case of fuse failure it should be replaced with a fuse of the same type 4 2 Battery assisted operation In case of a main power out...

Page 8: ...e are no technical possibilities to carry out the repairs or if the equipment has been conditionally accepted due to the breaking warranty terms by the claimant 7 All the services are carried out at the service centre of the manufacturer exclusively 8 The warranty does not cover the defects of the equipment resulting from reasons beyond the manufacturer s control mechanical damage improper storage...