background image

www.pulsar.pl

    

 

 

 

RUPS1612RT   

 

 

RACK POWER CCTV

 

 

 
 
CONTENTS: 
1. Technical description. 

1.1. General description 
1.2. Block diagram 
1.3. Description of PSU components and connectors 
1.4. Specifications 

2. Installation. 

2.1. Requirements 
2.2. Installation procedure 

3. Operating status indication. 

3.1. LED indication 
3.2. Technical output 
3.3. Acoustic indication 

4. Operation and use. 

4.1. Overload or short circuit of the PSU output 
4.2. Battery-assisted operation 
4.3. Maintenance 

1.  Technical description. 
 

1.1.  General description. 

     The 

RUPS1612RT

 buffer power supply unit is designed for uninterrupted power supply of up to  16 HD cameras 

requiring stabilized voltage of 

12V DC (+/- 15%). 

The PSU has two circuits: 

1x4A/12V DC

 for supplying the recorder and 

16x0,75A/13,8V DC

 for both cameras. Current efficiency of the PSU amounts to: 

 

Output current 16x0,75A + 4A re 2A battery charge 

Total device c battery: 18A max. 

 
      In case of power decay, a battery back-up is activated immediately. The PSU is fitted with 16 outputs protected 

independently with glass fuse 1A and the output for the recorder is protected with the 4A glass fuse. The power supply is 
fitted  with  the  ALARM  output  of collective failure.  In  case  of failure,  relay  contacts  are  switched  automatically,  which  is 
accompanied by acoustic and optical indication (the corresponding led goes on). The power supply construction is based 
on  the  switch  mode  PSU  with  high  energy  efficiency  and  is  located  in  an  enclosure  adapted  for  mounting  in  standard 

RACK

 19

” cabinets.  

 

1.2.  Block diagram. 

 

 

Fig.1. The block diagram of the PSU. 

 

1.3.  Description of PSU components and connectors. 

 

Table 1. Elements of the PSU. 

Element no. 

 [Fig. 2, 3] 

Description 

 

AC

 

OK

 

– green LED, indicating the presence of 230V voltage 

 

DC

 

OK

 

– green LED, indicating the presence of DC voltage

 

 

TEMP 

– red LED, indicating too high temperature of the power supply (>70°C)

 

Summary of Contents for RUPS1612RT

Page 1: ...RUPS1612RT v 1 0 RUPS 13 8V 12V 20A TOPIC RACK mounted buffer power supply for up to 16 cameras and recorder EN Edition 2 from 30 03 2017 Supercedes the edition 1 from 15 03 2016 ...

Page 2: ...y charge current 2A batteries 1x17Ah 1x28Ah 1x40A 1x65Ah control of voltage presence at the AUX1 AUX16 outputs DVR acoustic indication of failure LED optical indication AC DC TEMP LoB ALARM AUX1 AUX16 DVR the ALARM technical output of collective failure relay type activated by 230V AC power loss low voltage of the PSU 11 5V activation of the output fuse in the camera power supply circuit activatio...

Page 3: ...0 75A 4A recorder 2A battery charge Total device current battery 18A max In case of power decay a battery back up is activated immediately The PSU is fitted with 16 outputs protected independently with glass fuse 1A and the output for the recorder is protected with the 4A glass fuse The power supply is fitted with the ALARM output of collective failure In case of failure relay contacts are switche...

Page 4: ...f the recorder BAT battery output ALARM technical output of collective failure relay BUZZER micro switch turning ON OFF of acoustic indication switch in the top position indication ON switch in the down position indication OFF F1 F16 glass fuses in the cameras AUX power supply circuits F1A FDVR glass fuses in the recorder DVR power supply circuits F4A 230V AC INPUT power socket 230V AC power cable...

Page 5: ...peration LED AC DC TEMP LoB ALARM AUX1 AUX16 Acoustic operation indication Piezoelectric indicator 75dB 0 3m The ALARM technical output of collective failure Relay type 1A 30VDC 50VAC The FMAINS fuse in the 230V power supply circuit T 6 3A FDVR fuse in the recorder power supply circuits F 4A F1 F16 glass fuses in the cameras AUX power supply circuits 16x F 1A Mechanical parameters tab 3 Enclosure ...

Page 6: ...on of the recorder 4A Maximum battery charging current is 2A Total device current battery 18A max As the PSU is designed for a continuous operation and is not equipped with a power switch therefore an appropriate overload protection shall be guaranteed in the power supply circuit Moreover the user shall be informed about the method of unplugging usually through assigning an appropriate fuse in the...

Page 7: ...oltage 11 5V GREEN LED on DC voltage in the AUX1 AUX16 output off no DC voltage in the AUX1 AUX16 output GREEN LED on DC voltage in the DVR output off no DC voltage in the DVR output 3 2 Technical output The power supply is fitted with the ALARM output of collective failure relay type A collective failure can be triggered by the following events 230V AC mains power failure Activation of the glass ...

Page 8: ...em During the battery assisted operation reducing voltage below 9 5V at the battery terminals will cause battery disconnection 4 3 Maintenance Any and all maintenance operations may be performed following the disconnection of the PSU from the power supply network The PSU does not require performing any specific maintenance measures In case of fuse replacement use a replacement of the same paramete...

Reviews: