background image

www.pulsar.pl

    

 

 

 

RUPS848T 

 

 

  

           

RACK POWER 

 

 

 

Fig.3. The view of the PSU. 

 
1.4.  Specifications. 

- electrical parameters (tab.2) 
- mechanical parameters (tab.3) 
- operation safety (tab.4) 
- operating parameters (tab.5)

 

 Electrical parameters (tab. 2). 

Mains supply 

176÷264V AC  

Current up to 

1,1A@230V AC max. 

Supply power 

243W max. 

Efficiency 

85% 

Power factor PF 

>0,95 @230V AC 

Output voltage 

44

V ÷ 54V DC – buffer operation 

38V 

÷ 54V DC – battery-assisted operation 

Output current 

8 x 0,5A + 0,5A battery charge 

Ripple 

150 mV p-p max. 

Battery charge current 

0,5A max. (+/-5%) 

Short-circuit protection SCP 

8 x F 0,5A, glass fuse 

Overload protection OLP 

105% ÷ 150% of the PSU power, automatic return 
or: 8 x F 0,5A 

Current consumption by PSU systems 

0,26A 

Overvoltage protection OVP 

>62V (activation requires disconnecting the load or supply 
for about 20s.) 

Battery circuit protection SCP and reverse  
polarity connection 

glass fuse 

Surge protection 

varistors 

Excessive discharge protection UVP 

U<38V (+/-5%) 

– disconnect of connection battery 

Optical indication of operation: 

LED: AC, DC, TEMP, LoB, 

ALARM, AUX1÷AUX8 

Acoustic operation indication: 

Piezoelectric indicator ~75dB/0,3m 

The ALARM technical output of collective failure 

Relay type: 1A@ 30VDC/50VAC 

F

MAINS

 

fuse in the power supply circuit 230V 

T 6,3A 

Summary of Contents for RUPS848T

Page 1: ...RUPS848T v 1 0 RUPS 54V 8x0 5A TOPIC RACK mounted buffer power supply EN Edition 1 from 16 08 2016 Supercedes the edition ...

Page 2: ...n 1 2 Block diagram 1 3 Description of PSU components and connectors 1 4 Specifications 2 Installation 2 1 Requirements 2 2 Installation procedure 3 Operating status indication 3 1 LED indication 3 2 Technical output 3 3 Acoustic indication 4 Operation and use 4 1 Overload or short circuit of the PSU output 4 2 Battery assisted operation 4 3 Maintenance 1 Technical description 1 1 General descript...

Page 3: ...D indicating too low battery voltage 46V LED ALARM red LED failure indication Green LED AUX1 AUX8 voltage indication at the AUX outputs AUX1 AUX8 independently protected outputs BAT battery output ALARM technical output of collective failure relay BUZZER micro switch turning ON OFF of acoustic indication switch in the top position indication ON switch in the down position indication OFF F1 F8 glas...

Page 4: ... max 5 Short circuit protection SCP 8 x F 0 5A glass fuse Overload protection OLP 105 150 of the PSU power automatic return or 8 x F 0 5A Current consumption by PSU systems 0 26A Overvoltage protection OVP 62V activation requires disconnecting the load or supply for about 20s Battery circuit protection SCP and reverse polarity connection glass fuse Surge protection varistors Excessive discharge pr...

Page 5: ... unacceptable Impulse waves during operation unacceptable Direct insulation unacceptable Vibrations and impulse waves during transport According to PN 83 T 42106 2 Installation 2 1 Requirements The PSU RACK shall be mounted by a qualified installer with appropriate permissions and qualifications for 230V AC installations and low voltage installations required and necessary for a given country The ...

Page 6: ...ply and turn on the power 230V 7 Check the PSU operation indicator 3 Operating status indication 3 1 LED indication The PSU has 13 LED lights at the front panel GREEN LED on the PSU is supplied with 230V AC off no 230V AC supply GREEN LED on DC voltage at the output of the switch mode PSU off no DC voltage at the output of the switch mode PSU RED LED on failure off no failure RED LED ON too high t...

Page 7: ... the switch switch in the up position indication ON switch in the down position indication OFF 4 Operation and use 4 1 Overload or short circuit of the PSU output The AUX1 AUX8 power supply outputs are protected against short circuit with glass fuses If a fuse assisted protection has been chosen replace the fuse of the same parameters in case of a failure 4 2 Battery assisted operation In case of ...

Page 8: ...l household waste According to the European Union WEEE Directive waste electrical and electronic equipment should be disposed of separately from normal household waste Pulsar Siedlec 150 32 744 Łapczyca Poland Tel 48 14 610 19 40 Fax 48 14 610 19 50 E mail biuro pulsar pl sales pulsar pl http www pulsar pl www zasilacze pl ...

Reviews: