                   SWB series                                                 

 

 

 

2. Installation. 
 

2.1 Requirements. 

Device is to be mounted by a qualified installer, holding relevant permits and licenses (applicable and required 

for  a  given  country)  for  ~230  V  in  and  low-voltage  installations.  The  unit  should  be  mounted  in  confined  spaces,  in 
accordance with the II environmental class, with normal relative humidity (RH=90% maximum, without condensing) and 
temperature from -

10°C to 40°C.  

As power supply is designed for a continuous operation and is not equipped with a power-switch, therefore, an 

appropriate  overload  protection  in  power  supply  circuit  should  be  provided.  Moreover,  user  should  be  informed  how  to 
disconnect power supply unit from mains supply (most frequently through separating and assigning an appropriate fuse in 
the fuse-box).  

 

2.2 Installation procedure.

  

 

CAUTION! 
Before installation, cut off voltage in 230 V power-supply circuit. To switch power off, use an 
external switch, in which distance between contacts of all poles in disconnection state is not 
less than 3mm. 
 

         It  is required  to  install  an  installation  switch with  a  nominal current  of  min.  3  A  in  the  power  supply 
circuits outside the power supply unit. 

 

1.  Mount the device  in a selected location and connect the wires.  
2.  Connect the power cables (~230 V) to L-N clips of the PSU. Connect the ground wire to the clip marked by the 

earth symbol 

. Use a three-core cable (with a yellow and green protection wire) to make the connection.  

Lead the cables to the appropriate clips through the insulating bushing of the PSU.

 

 

 

 

Shock protection circuit shall be done with a particular care: yellow and green wire coat 

of  power  cable  should  be  connected  to  terminal  marked  with  the  grounding  symbol  on  PSU 
enclosure. Operation of PSU without the properly made and fully operational shock protection 
circuit is UNACCEPTABLE! It can cause damage to equipment or an electric shock.

 

 

3.  Connect battery in correct polarity. 
4.  Make the selection is done with use of the IBAT jumpers (see: tab.1) 
5.  Screw brackets to devices and install them inside enclosure. 

Remember to place devices starting from rear of enclosure. 

6.  Connect switch using cable terminated with a DC 2.1/5.5 plug. 
7.  Mount inside enclosure. 
8.  Connect the power 230 V  
9.  After installing and checking proper working, the enclosure can  

be closed.  

 
 

3.  Maintenance.  

Any and all maintenance operations may be performed following the disconnection of the PSU module from the 

power supply network. The PSU does not require performing any specific maintenance measures, however, in the case 
of significant dust rate, its interior is recommended to be cleaned with compressed air. In the case of a fuse replacement, 
use a replacement of the same parameters.  

 

 

WEEE LABEL 

Waste electrical and electronic equipment must not be disposed of with normal household waste. 

According to the European Union WEEE Directive, waste electrical and electronic equipment 

should be disposed of separately from normal household waste. 

 

CAUTION!

 

The power supply unit is adapted for cooperation with the sealed lead-acid batteries (SLA). After the operation 

period they must not be thrown but recycled according to the applicable law. 

 

 
 

Pulsar sp. j.  

Siedlec 150,  32-744 Łapczyca, Poland 

Tel.  (+48) 14-610-19-40, Fax. (+48) 14-610-19-50 

E-mail: 

biuro@pulsar.pl

sales@pulsar.pl

 

http:// 

www.pulsar.pl

www.zasilacze.pl

 

Summary of Contents for SWB-300RACK

Page 1: ...USER MANUAL EN Edition 1 from 24 09 2020 Supersedes the edition SWB 300RACK Buffer power supply system for PoE switches RACK 3U 54VDC 4x17Ah 300W ...

Page 2: ...ations 2 Installation 2 1 Requirements 2 2 Installation procedure 3 Maintenance 1 Technical description 1 1 General description Buffer power supply system for PoE switches SWB 300RACK is designed for uninterrupted power supply of PoE switches with 54 V DC It was designed based on high energy efficiency switching power supply module placed in metal enclosure color RAL 9003 Enclosure has a place for...

Page 3: ... Brackets for mounting straps 4 Cable bushing 5 TAMPER microswitch of antisabotage protection NC 6 Power cable terminated with EDG 5 08 2P plug DC 2 1 5 5 reduction included 7 BAT BAT battery output BAT red BAT black 8 Selection jumper for charging current J1 J2 J3 Ibat 0 5 A J1 J2 J3 Ibat 1 A J1 J2 J3 Ibat 2 A Description jumper installed jumper removed 9 Mounting holes to install additional moun...

Page 4: ...90 without condensation Dimensions W 535 H 540 D 165 mm 2 W1 540 H1 545 D1 14 mm 2 W2 530 H2 380 D2 155 mm 2 H3 360 or 304 or 248 mm 2 Enclosure Steel sheet DC01 1 2mm color RAL 9003 Closing Cheese head screw x 2 at the front possibility of installing two locks with different codes Notes Enclosure does not adjoin assembly surface so that cables can be led Additional equipment Mounting screws x4 Ne...

Page 5: ...all be done with a particular care yellow and green wire coat of power cable should be connected to terminal marked with the grounding symbol on PSU enclosure Operation of PSU without the properly made and fully operational shock protection circuit is UNACCEPTABLE It can cause damage to equipment or an electric shock 3 Connect battery in correct polarity 4 Make the selection is done with use of th...

Reviews: