Table 2. Specifications. 

Power supply 

~ 200 

– 240 V; 1 A; 50/60 Hz 

Inrush current 

40 A 

Efficiency 

82% 

PoE supply 

52 V DC; 60 W 

Ripple voltage 

100 mV p-p max. 

Battery charging voltage 

11-13,8 V DC 

Battery charging current 

1 A / 2 A jumper selectable 

Short circuit protection (SCP) 

electronic, automatic recovery 

Overload protection (OLP) 

105 

– 150% of power supply, automatic recovery 

Surge protection 

varistors 

Current consumption by PSU 
during battery-assisted operation

 

about 40 mA 

LED optical indication output 

LED AC - presence of AC voltage  

LED DC - presence of DC voltage in the output of the PSU 

LED CHARGE - battery charging process 

Connectors 

Power input: 

Φ0,63-2,50 (AWG 22-10) 

PoE power supply output: DC plug 2.1/5.5 

BAT output: battery wires 6,3F 

– 45cm, angle muffs ML062 (hole 5,2 mm) 

Operating conditions 

Temperature -

10°C ÷ 40°C, 

Relative humidity 5%-90% without condensation 

Dimensions 

W=300, H=300, D+D

1

=105+8 [+/- 2mm] 

W

1

=305, H

1

=305 [+/- 2mm]  

W

2

=230, H

2

=110, D

2

=45  [+/- 2mm] 

Enclosure 

Steel sheet, DC01 0,7mm color RAL 9003 

Closing 

Cheese head screw x 2 (at the front, lock assembly possible) 

Notes 

Enclosure does not adjoin assembly surface so that cables can be led. 

Additional equipment 

Mounting screws (x4) 

Net / gross weight 

2,75 / 2,88 [kg] 

Declaration 

CE 

 
Table 3. Operation safety. 

Protection class EN 62368-1 

I (first) 

Degree of Protection EN 60529 

IP20 

Electrical strength of insulation: 
- between input input and output circuits of the PSU 
- between input circuit and protection circuit 
- between output circuit and protection circuit 

 
2500 V AC min. 
1500 V AC min. 
  500 V AC min. 

Insulation resistance: 
- between input circuit and output or protection circuit 

 
100 MΩ, 500 V DC  

 
Table 4. Operating parameters. 

Environmental Class 

II 

Operating temperature 

-10

ºC...+40ºC  

Storage temperature 

-

20ºC...+60ºC 

Relative humidity 

20%...90%, without condensation 

Vibrations during operation 

unacceptable 

Impulse waves during operation 

unacceptable 

Direct insulation 

unacceptable 

Vibrations and impulse waves during transport 

Wg PN-83/T-42106 

 

2. Installation. 
 

2.1 Requirements. 

Device is to be mounted by a qualified installer, holding relevant permits and licenses (applicable and required 

for  a  given  country)  for  ~230  V  in  and  low-voltage  installations.  The  unit  should  be  mounted  in  confined  spaces,  in 
accordance with the II environmental class, with normal relative humidity (RH=90% maximum, without condensing) and 
temperature from -

10°C to 40°C.  

As power supply is designed for a continuous operation and is not equipped with a power-switch, therefore, an 

appropriate  overload  protection  in  power  supply  circuit  should  be  provided.  Moreover,  user  should  be  informed  how  to 
disconnect power supply unit from mains supply (most frequently through separating and assigning an appropriate fuse in 
the fuse-box).  

 
 
 
 
 
 
 

Summary of Contents for SWB-60

Page 1: ...USER MANUAL EN Edition 1 from 24 09 2020 Supersedes the edition SWB 60 Buffer power supply system for PoE switches 52VDC 7Ah 60W ...

Page 2: ...n procedure 3 Maintenance 1 Technical description 1 1 General description Buffer power supply system for PoE switches SWB 60 is designed for uninterrupted power supply of PoE switches with 52 V DC It was designed based on high energy efficiency switching power supply module placed in metal enclosure color RAL 9003 DC DC converter used to increase voltage allows to reduce costs of system by limitin...

Page 3: ...e 4 Cable bushing 5 TAMPER microswitch of antisabotage protection NC 6 Switch power cable terminated with a DC 2 1 5 5 plug 7 BAT BAT battery output BAT red BAT black 8 Selection jumper for charging current Ibat 1 0 A Ibat 2 0 A Description jumper installed jumper removed Fig 3 View of PSU 1 4 Specifications electrical parameters tab 3 mechanical parameters tab 4 operation safety tab 5 operating p...

Page 4: ...tion class EN 62368 1 I first Degree of Protection EN 60529 IP20 Electrical strength of insulation between input input and output circuits of the PSU between input circuit and protection circuit between output circuit and protection circuit 2500 V AC min 1500 V AC min 500 V AC min Insulation resistance between input circuit and output or protection circuit 100 MΩ 500 V DC Table 4 Operating paramet...

Page 5: ...age to equipment or an electric shock 4 Connect battery in correct polarity 5 Make the selection is done with use of the IBAT jumpers see tab 1 6 Screw switch to mounting plate 7 Connect switch using cable terminated with a DC 2 1 5 5 plug 8 Mount inside enclosure 9 Connect the power 230 V 10 After installing and checking proper working the enclosure can be closed 3 Maintenance Any and all mainten...

Reviews: