background image

www.pulsar.pl 

                SWS series                                                 

 

 

 

2.2 Installation procedure.

  

 

CAUTION! 
Before installation, cut off voltage in 230 V power-supply circuit. To switch power off, use an 
external switch, in which distance between contacts of all poles in disconnection state is not 
less than 3mm. 
 

         It  is required  to  install  an  installation  switch with  a  nominal current  of  min.  6  A  in  the  power  supply 
circuits outside the power supply unit. 

 

1.  Mount the device  in a selected location and connect the wires.  
2.  Remove mounting plate by unscrewing screws, then release plate from hooks (slide up and slightly pull). 
3.  Connect the power cables (~230 V) to L-N clips of the PSU. Connect the ground wire to the clip marked by the 

earth symbol 

. Use a three-core cable (with a yellow and green protection wire) to make the connection.  

Lead the cables to the appropriate clips through the insulating bushing of the PSU.

 

 

 

 

Shock protection circuit shall be done with a particular care: yellow and green wire coat 

of  power  cable  should  be  connected  to  terminal  marked  with  the  grounding  symbol  on  PSU 
enclosure. Operation of PSU without the properly made and fully operational shock protection 
circuit is UNACCEPTABLE! It can cause damage to equipment or an electric shock.

 

 

 

4.  Check output voltage and adjust if necessary using potentiometer. 
5.  Screw switch to mounting plate.  
6.  Connect switch using cable terminated with a DC 2.1/5.5 plug. 
7.  Mount inside enclosure. 
8.  Connect the power 230 V 

 

9.  After installing and checking proper working, the enclosure can be closed.  

 

3.  Maintenance. 

Any and all maintenance operations may be performed following the disconnection of the PSU module from the 

power supply network. The PSU does not require performing any specific maintenance measures, however, in the case 
of significant dust rate, its interior is recommended to be cleaned with compressed air. In the case of a fuse replacement, 
use a replacement of the same parameters.  

 

 

 

WEEE MARK 

According to the EU WEE Directive – It is required not to dispose of electric or electronic waste as unsorted 

municipal waste and to collect such WEEE separately.

 

 

 

 

CAUTION! 

The power supply module unit is adapted for a sealed lead-acid battery (SLA). After the operation period it must not be 

disposed of but recycled according to the applicable law.

 

 

Pulsar sp. j. 

Siedlec 150, 32-744 Łapczyca, Poland 

Tel. (+48) 14-610-19-40, Fax. (+48) 14-610-19-50 

e-mail

biuro@pulsar.pl

sales@pulsar.pl

 

http:// 

www.pulsar.pl

www.zasilacze.pl

 

 

Summary of Contents for SWS-150

Page 1: ...USER MANUAL v1 1 EN Edition 2 from 25 05 2022 Supersedes edition 1 from 24 09 2020 SWS 150 Power supply system for PoE switches 52VDC 150W ...

Page 2: ...n SWS 150 is designed for uninterrupted power supply of PoE switches with 52 V DC It was designed based on high energy efficiency switching power supply module placed in metal enclosure color RAL 9003 Enclosure is equipped with a tamper switch signaling opening the door front panel Device is equipped with removable universal mounting plate which allows to mount PoE switches with dimensions up to 2...

Page 3: ...www pulsar pl SWS series 3 Mounting plate W2xH2 Fig 3 View of PSU 1 4 Specifications electrical parameters tab 3 mechanical parameters tab 4 operation safety tab 5 operating parameters tab 6 ...

Page 4: ... input circuit and protection circuit between output circuit and protection circuit 2500 V AC min 1500 V AC min 500 V AC min Insulation resistance between input circuit and output or protection circuit 100 MΩ 500 V DC Table 4 Operating parameters Operating temperature 10ºC 40ºC Storage temperature 20ºC 60ºC Relative humidity 20 90 without condensation Vibrations during operation unacceptable Impul...

Page 5: ...perational shock protection circuit is UNACCEPTABLE It can cause damage to equipment or an electric shock 4 Check output voltage and adjust if necessary using potentiometer 5 Screw switch to mounting plate 6 Connect switch using cable terminated with a DC 2 1 5 5 plug 7 Mount inside enclosure 8 Connect the power 230 V 9 After installing and checking proper working the enclosure can be closed 3 Mai...

Reviews: