PULSAR MEASUREMENT
41
PARAMETER
DEFAULT
DESCRIPTION
P213 / P214
Relay 1 ON/OFF
setpoints
Factory preset as a % to
appropriate level according
to the span already
entered. See tables below
Either Alarm or Level control.
Depends on application.
P223 / P224
Relay 2 ON/OFF
setpoints
Factory preset as a % to
appropriate level according
to the span already
entered. See tables below
Either Alarm or Level control.
Depends on application.
P233 / P234
Relay 3 ON/OFF
setpoints
Factory preset as a % to
appropriate level according
to the span already
entered. See tables below
Either Alarm or Level control.
Depends on application.
P243 / P244
Relay 4 ON/OFF
setpoints
Factory preset as a % to
appropriate level according
to the span already
entered. See tables below
Either Alarm or Level control.
Depends on application.
P253 / P254
Relay 5 ON/OFF
setpoints
Factory preset as a % to
appropriate level according
to the span already
entered. See tables below
Either Alarm or Level control.
Depends on application.
P263 / P264
Relay 5 ON/OFF
setpoints
Factory preset as a % to
appropriate level according
to the span already
entered. See tables below
Either Alarm or Level control.
Depends on application.
P830 mA Out Range 2 = 4 to 20mA
Determines the mA output
range.
0 = Off, 1 = 0 to 20mA,
2 = 4
to 20mA
, 3 = 20 to 0mA, 4 =
20 to 4mA.
P870 Fill Damping
10m/min
Rate of maximum fill rate (set
above the actual fill rate of the
vessel).
P871 Empty
Damping
10m/min
Rate of maximum empty rate
(set above the actual rate of
the vessel).