ZENITH 140
INSTRUCTION MANUAL
130
3 = Xducer 2
Displays level from transducer 2
P816 Totaliser (R)
This parameter determines whether the resettable totaliser will be displayed
in the auxiliary line of the display in run mode. When selected, the auxiliary
display will scroll between the resettable totaliser and the totaliser units
selected.
Default = 0 (Off).
When being used to totalise Flow the resettable totaliser can be reset whilst
in run mode via the “Totaliser” hot key
by pressing “0” whilst Total (R) is
displayed.
P817 Auxiliary Offset
The value of this parameter is added to the reading of the auxiliary display
before it is displayed, in
Measurement Units
(
P104
).
Totaliser
P820 Totaliser
Displays the current value of the, non-resettable totaliser. During run mode
this totaliser can be viewed via the “Totaliser” hot key,
. Unlike the
resettable totaliser this totaliser cannot be reset whilst in run mode, it can
however be reset whilst in program mode by accessing
P820 Totaliser
and
entering
zero
.
P821 Totaliser (R)
Displays the current value of the, resettable totaliser. This
totaliser
can be
allocated to appear, during
run mode
, on the auxiliary display line (
P816
) or
alternatively via the “Totaliser” hot key.
P822 Totaliser Decimal Places
This parameter determines the number of decimal places in the totaliser
during run mode. It can be set between 1 and 3.
Default = 2