Corporate
800.882.8854
81
F008
Description:
Overtemp fault
Translation:
The VFD is too hot to run.
Solution:
Verify the fans are running. Check parameter
D024, it will display the VFD temperature in Celsius. If
fans are working, check hole size on the drain portion and
increase hole size but do not exceed 3/8”.
This fault will automatically reset.
Description:
Hardware Overcurrent fault
Translation:
There is too much current going out to the
motor.
Solution:
Check amp draw, verify wiring is snug in motor
junction box and on VFD screws.
This fault will not automatically reset.
F012
F013
Description:
Ground fault
Translation:
There is a leak to ground detected on the VFD
output to the pump.
Solution:
Try to reset, if fault will not reset, power down,
disconnect pump and check and see if fault is still present.
If not, check motor connections in motor junction box and
replace pump if needed.
This fault will not automatically reset.
F033
Description:
Auto restart timeout fault
Translation:
The VFD had a different fault, tried to reset it
automatically twice and could not.
Solution:
Press stop button, if fault clears check D007
through D009 for the last 3 VFD faults that occurred to
find the cause of the fault number that caused the original
problem.
This fault will not automatically reset.
F122
Description:
I/O Board Fail
Translation:
There is a problem detected with one of the
circuit boards on the VFD.
Solution:
Turn VFD off and then back on to see if problem
clears itself. If not, the board or the drive will need to be
replaced.
This fault will not automatically reset.
VFD Fault Information