PureAire Monitoring Systems, Inc.
27
5.5.2 Set Formats
This is the menu at which to adjust the relay states for the two gas alarm relays and
the individual instrument fault relay.
Push the joystick down to access the next main menu,
Set Formats.
The display will
scroll the following:
This menu will permit the setting of the two alarm relays and the fault relay settings
from normally de-energized state,
Normal
, to normally energized state,
Inverted.
From this main menu, pushing the joystick to the right will select the sub menu and the
digital display will scroll the following:
This is the menu at which to adjust the first level alarm relay state on the Universal
Gas Detector. To change this value, push the joystick right to display the relay state.
The display will indicate
NORMAL.
Pushing the joystick down will change the relay
state from NORMAL to INVERT.
(NOTE: If inverted, the Alarm 1 LED will
illuminate).
Push the joystick left once to exit this menu.
After entering the relay state by pushing the joystick left, the display will default back
to the Set Formats Relay 1menu. The display will scroll the following:
…Set Formats…
0.0 ppm
..Format Relay 1…
0.0 ppm
NORMAL
0.0 ppm
INVERT
0.0 ppm
..Format Relay 1…
0.0 ppm